Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

In power generator sets, when they are coverted from 50hz
to 60hz, the kva rating after conversion increases. For
example, the manufacturer of a perkins 200kva @ 50Hz
generator set has mentioned it to become 220kva after
converstion to 60hz. What is the relation between the
frequency & the KVA rating. Any formula please.

Answer Posted / kj

The main reason for the increase in the kva is that the
diesel engine produces more HP at 1800 rpm than at 1500 rpm.
This allows a higher kw output. The alternator can also
handle the higher current and therefore the kva is
increased. Note that the rated power factor stays the same.
This is because the amount of cooling air is increased at
the higher speed.
The increase in the EMF per turn allows a higher voltage to
be generated but this is reduced by the AVR reducing the
excitation. This has no effect on the kva capacity of the
generator set.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the meaning of 40X8X2 busbar dimensions for carring load of 400 Amps

2048


In what cases (circumstances)we should apply P controller, PD controller, PI controller & PID controller ?

2234


Why we use Electrical energy rather than any other type of energy, mostly? Explain behavior of open secondary CT and short circuited secondary PT in energized condition?

1944


How LT megger works ?

2184


How is magnetic leakage reduced?

1236


What does the term “voltage regulation” means?

1178


Anyone who can recommend an equivalent to Envirotemp FR3 of Cooper?

2024


I have 440v power coming to facility,( not being used ) can I buy large generator, (gas) to sell power back to electrical co.

2518


If a shunt Dynamo has induced emf 100V and 0.4 ohm resistance and battery of accumulator of open circuit emf 110V and 0.5 Ohm resistance are in parallel what is common terminal potential difference?

5309


at what base you will tell the direction of rotation of dc motors and generators?

1179


"TRANSFORMER MODELING AND ANALYSIS" MEANS WHAT AND WHICH TOPICS U READ IN THIS

1945


What are the Formula of computing Back up Time of 500kVA UPS with 4 Battery Banks, each bank composed of 43 pcs of Batteries 12V150Ah. How to compute the Back up Time of UPS? We have also 3X500kVA UPS running in Parallel same composition as I write above.

1402


mccb service sittings be done?

1863


what is the basic construction diffrance between servo motor ans sqiralcage induction motor

2554


How to decide no. of Step and Kvar for APFC Panel 40 kvar MD: 33.12 KVA Avg pf : 0.8540

1146