I work on a electronic positioner transmitter 4211 at the
field.I connect my multimeter in series to get the current
output then I calibrate it to 4ma in 0% of position of the
valve and 20ma in 100% position of the valve.My problem is
in the field I get the correct output current based on my
multimeter but in the dcs they only receive 40% in a output
20ma of this positioner.Then I try to simulate in this
analog card and they receive the equivalent percent on the
value that I simulated.Is ther any possibility to reset the
zero and span of this positioner 4211 fisher.And what other
possibility I can do to fixed this.This is my email add (
landicho_randy@yahoo.com )
Answer Posted / sks
you should check that your AI channel might consist of 3
terminals, 1+,1-, COM. this is the facility provided to
connect both voltage(0-10V) or current(4-20ma) analog signal
introducing to AI module/card.
since you are using current i/p(4-20ma) 1- & COM channels
must be looped with 250ohm resistance first. this might
solve your problem.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Can anyone send most commonley asked Instrumentation questions and answers in cement industry please?
what is commisioning procedure,2)what is is the main work in commisioning in the field tx to dcs, plz send me detail
I want to measure and control level in tank of size 10*5 filled with gasoline, so plz give me the solution with clear details. how to select transmitter and sensors.
I am having a Phoenix digital to modbus converter. The o/p of the same is connected to flow computer FB407. But the digital signals are updated only after one minute in the flow computer. what may be the cause of delay in communication? Flow computer is having a scanning period of less than 1 sec.
what is the difference between active & reactive power?
What is the Working principle of Dozing valve?
What is the procedure of calibration of Load cell?
what is instrument philosophy
flow transmitter formula?
Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.
Can anyone send most commonly asked interview question in Oil & Gas industry
Actual using of tube bender to bend 2 opposite 90 deg at correct measurement center to center of tubing.
how to calculate the total flow in square root
what is the diffrence between pressure safety valve & pressure relief valve....pls
where uses EXe /EXd/Exo/Exn/Exp/Exq/EXia