Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

T.x range -0.1 to 0.2 milibar,so how much mili ampear at 0.1 milibar?

Answer Posted / karthikeyan kvp

TX range is -0.1mbar to 0.2mbar

span= maximum-minimum
= 0.2-(-0.1)
= 0.3

mA = given value- zero value/ span x 16+4

= 0.1-(-0.1)/0.3 x 16+4

= 0.2/0.3 x 16+4

= 14.66 mA

Is This Answer Correct ?    8 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What are the types of control valves available

2108


how to control pid

1912


what is a vortex flow meter,mass flow meter and electromagnetic flow meter.particular use of this.means in which condition particular meter is used.

2238


1.can you use SCADA instead of DCS,DCS instead SCADA 2.Difference between DCS and PLC,can their role be reversed i.e. role interchange 3.Difference between RTU and PLC

2594


Explain why plc require in analog input 4-20amp & 0-10 volt?

1096


1)How many tpes of vibration probe and how many tpyes of vibration. 2)how we can calibrate a vibration probe with tk3 3)what is RMS value in vibration measuring application and how we calculate it.

2421


Why plc require in analog input 4-20amp & 0-10 volt?

1139


How to calibrate H2s Dectector

1618


What is limitation of the ht.of the displacer of a level trol?

2396


A flange is used for instrument connection for a system with a design temperature of 316C (600F) and a design pressure of 1000 kPa (145 psi). What is the class rating of the flange to be used for this application? Explain your answer

2651


In my company plc based winders are operated. one day there was a data transmission failure alarm shown on pc. as per sir instruction we have reset master plc but winders were not triped and alarm gone. so what master plc do?

1866


How many types of sensor

1616


Draw block digram for well head from well to shipping pump?

2173


How an rtd work, and what volts/current goes to a rtd to measure the resistance?

1278


how to convert MA in to measuring values..and how mwasuring values into MA ?..plz ansr.i have intervw

2656