Answer Posted / rajagopal
1.If there is no hp/lp bypass when the turbine is tripped and still boiler will be in service all the generated steam has to to evacuated by opening SH/RH vents.In presence of bypass system even when turbine is tripped we can possible to bypass the steam and dump it into condenser.
2.the major advantage of doing the above is we can maintain the boiler in hot condition with minimum steam generation cold start up and preservation after shutdown is quite difficult.
Is This Answer Correct ? | 28 Yes | 0 No |
Post New Answer View All Answers
what is the difference between compensated & normal drum level in boiler drum?
what is natural frequency of turbine shaft .
procedure of how to generate power in solar plant.
what is restricted earth fault explain in details
Why superheated are started before I'd and rd fan?
what is the trip circuit supervision in an electrical meaning?
We have Demin Closed cooling water system with expansion tank for cooling oil system. Expansion tank having N2 bladder. Whenever N2 bladder bursts out, Closed cooling water circuit pressure drops and make-up happening, eventhough there is no leaks. And how Circuit pressure drops?
what does mean by kva rating
How We Calibrate the vaccum transmitter?
operation
How to calculate boiler capacity? I have 1 Autoclave, Which has to use for AAC block. Dimension for this Autoclave is - 13 Meter Length & 2.2 Meter Diameter.
LAPT working in alternator / generator
By any way can we increase the B check hours from 300 to 500
why do you consider yourself a suitable candidate for this position
dear sir i have completed one year post diploma certificate in thermal power engineering from national power training institute durgapur ...plz suggest me for power sector job