Good Evening all.My question is - For a feed water line to
an equipment if i need to measure the flow we will use
orifice /magnetic/vortex depend on cost/spec.If i need to
measure a ''Alarm''signal and ''Interlock'' from one point
i think we can use orifice type in one location with 2
different tapping points - one for alarm and one for an
interlock to flow valve..If in case i need to have both
these signals(Alarm & interlock) from magnetic flow
meter,is it possible??will 2 seperate sensors will be
located inbuilt r we can program it ??..i thk we can have
one transmitter with these 2 signals...need to know any
technical issues are there?pls clarify

Answer Posted / carl_ellis

It seems you are using a flow meter's relay(s) to generate
alarm signals at various amplitudes: low, low/low, hi,
hi/hi.

The flow meter doesn't really use these alarm signals
itself, rather it generates the alarm signals and provides
the alarm signals to other devices, for whatever purpose,
alarm, annunciation or an interlock.

There might be a flow meter with 3 alarm relays. I don't
know. That's a shopping issue.

Most places will use a PLC, a controller or a DCS to
generate alarms from the analog flow signal.

But if your flowmeter doesn't have enough relays, then use
a "DC alarm trip" I/O module with the flow meter's 4-20mA
analog output.

The modules have an analog input and one or two relay
outputs with adjustable setpoints. There's probably a
dozen models on this page:
http://www.api-usa.com/signalconditioners_alarms.php

These I/O modules are not used "in a magmeter", they're
external I/O modules.

They place a small burden resistance in the 4-20mA circuit,
need an enclosure and AC or DC power to operate, but they
accomplish the task of providing multiple alarms at various
setpoints.

The 4-20mA signal is wired in series with the I/O module
and any other receiver devices.

Carl Ellis
Measure First

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Questions on flow meters,few questions on HART protocol,

1571


What is the difference bitween control net scaner and device net scaner

2953


what is the advantage of submersible level transmitter compare to ultrasonic level transmitter?

1623


What should be the main consideration while starting the Rotating compressor when we dont know the cut in and the cut off pressure setting of the pressure switch

1698


How to convert milliampares into flow??

1273






why we use cascade control and feed foreword control in 3 element control of boiler drum ?what is feed forward and cascade control system ?

1756


what happen if i increase height of displacer type LT.accuracy or sensitivity are affected.why?

2070


Define the terms Accuracy, precission, Spam, process tolerance while doing calibration of an instrument? Explaini with an example?

1564


What is zener diode? What is voltage regulator?

641


Capacitance, resistance ( colour coding ), parallel & series circuits.

1733


I WANT SECURITY PAPER MILL, HOSHANGABAD TEST PAPER.KINDLY SEND TO MY MAIL ID

2294


give some question relative instrument fitter?

5791


what are the values of fuel flow rate in various places in boiler.

1234


how to calculate control valve bonnet size?? or how to select its material?

1953


What is rang ability?

1790