Answer Posted / wareagle
Vipul Kumar your answer is wrong.
W is not = 1.732x380xI. W =1.732x380xIx PF. You left off
the power factor
Bala your answer is wrong also.
KA is not equal power/ (1.732*400*% of Impedance)Note
spelling of impedance. Where did you go to school?
Amps = 30 KVA/ (0.380 x 1.73)or 30000 va/380 x 1.73
Amps = 46
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
what are the range of memory address in plc for L&T lx7 4A
How to findout raw or ups power? its not indicated in socket,
How can we decide cable size from HT panel to Transformer? Please give you reply with some examples.
what are the pecularity of shaver sockets ?
What are the conditions for sustained oscillator or what is backhouse criterion?
how a.c. genarator control power factor when its conected to grid supply by incrising or decresing excitation voltage.
Explain about Dubai electrical sysaem? Explain about Dubai drinking water system? Explain about Dubai Burj tallest building Electrical,Water.etc.. maintenance system?
how to calculate the size of the HT cable
What is big transformer parts and their function ? Ty
What is transient Phenomenon?
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
how to find ratio of CT & PT in 66/11kv 12 mva supply system ? explain with calculation.
WE ARE PLACE A NEW 75 KW MOTOR FOR JPF.IT IS CONNECTED IN M.C.C. WHEN WE ARE STARTING M.C.C.INCOMER IS TRIPPED.THEN WE ARE CONNECTED IN P.C.C WITH A MM30 RELAY PROTECTION THEN WE ARE STARTED MOTOR WILL RUN SMOOTHLY.
How many turns are there in primary winding? (In Transformer)
Formulae for calculating the transmission line losses for different voltage levels