yokogawa Temperature transmitter showing Error 15 which is Reverse Cal Fail (confirmation calculation result is bad) in manual they mentioned reasion That the output goes to the value set by hardware failure mode jumper. How can solve this problem ? anybody can say solution
Answer Posted / carl_ellis
In the manual (from which you cited) the user action for
error 15 is 'contact service personnel'.
You can try that, but I suspect that it means, for all
practical purposes, replace the transmitter. I don't know
if Yoko offers a spare 'puck' that can be replaced in order
to salvage the housing and display, or not. You'll have
to ask.
You might try cycling power to it to see if an electrical
spike on the loop wiring adversely affected the processor,
and cycling the power might re-initialize it, but the
likelihood of success is very small.
When a transmitter goes to fail-safe mode, it's usually the
last act of the last performance, the actors are clasping
hands, and taking a final bow before the show closes.
tell 'em Carl sent you
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
What is standard of DCS panel design?and what is step of DCS panel design?wiring and type of connector(screw or DB connector)
Explain about safety integrated level protection? . How it was differ from other protections ?
Reason for capillary type dp level transmitter fluctuation
how to connect transmitter measuring sulfur process? 1-by using long impulse line or 2- by using coated short impulse line
Hi i am aneesh, done btech in applied electronics & instrumentatiin. And then i took mba in finance & marketing.After that i got placement in finance co and worked there for 3.5 yrs.Now i wanted to come back to engineering job.But without engg experience, i may not able to find an opening.i have done a course related to flow meters and ite calibrations. Kindly suggest where should i try to get a job?
What is difference between ESD and PLC please Explain me clearly.
What is the minimum rating availalbe for weld neck orifice in market?
What is sensitivity in vibration probes..?
Which are all the commonly used Bordon tubes in the pressure gauges. Do any one use ASTM A 312 tubes for this purpose?
What are the interlocks we have to check during the start up of LP/HP compressor?
what are the documents(Construction point of view for a process plant) submitted by contactor initially entering in to new site for client?
Why thermo wells are used? What materials are used in thermo wells?
How will you calibrate PID controller? explain with example.
Can I calibrate the Electromagnetic Flow Meter on line and How.
what is your eligibility criteria for freashers?