In the UVR(Under Voltage Relay) there is a knob for the
hysteresis setting. what is this setting? its threshold is
given from 5% to 50%. please help me....
Answer Posted / kj
The hystersis is the difference between the voltage at
which the relay operates at and resets at.
For example the UVR is set to open the contacts at 200
volts and it can be set to close at 211.5 volts (for 230
volt sensing). This would be 5% hystersis setting.
This is to stop the relay switching on and off continuously
when the voltage is around 200 volts.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What are reasond for high wattage in single phase induction motors
how are reversing the direction of rotation of dc motor
What is the basic principle of welding process?
how electrical earthing maintenance done in industry?
comparision between ACB and VCB
How many size of cable required for a 300m long and 30kw inductive lode
What are the raitings of Mcb,mccb and Acb in detail ??
What is proportional controller?
hi....I am from india..i have completed my engineering in electrical and electronics field with 58.4% and my IELTS score is 5.5 bands....Recently i received my I-20 in computer and information science from Troy university in Alabama.On 18th i have a visa interview can u please tell me what type of questions i have to answer ??????