If the neutral wire go pass through the core balance current
transformer? If yes then why? and no then why?
Answer Posted / kj
The neutral is requiered to pass through the core balance
CT together with the phase for the same circuit. It
operates on the current going through the pahse being
balanced with the current returning through the neutral. If
these are balanced the protection will not operate. If a
fault occurs (a short circuit to earth in either the phase
or neutral)some current will flow through the earth to the
neutral and not go through the CBCT. This will then operate
the protection.
| Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
Mr. mohh sahid m not satisfied for ur answer to the que weather the size of transformer increases or decreases withchange in fr for more detail go to the answer given by me
what are the analog quality input for protection function?what are minimum reqiments?
How do you compute voltage drop and cable size over distance?
2- What are the percentages between excitation currents in phase (R, S and T) in ∆ and Ỵ connections in excitation Current test in transformers?
why we use ac supply as 415 volts instead of 415 v why we cant apply 230 v for dc
What does the kvar means?
Why strting torqe high in inducation motor?
What is the height of DA, DAL, DB, DC & DDE tower?
How Self works in DG set
Why you are switching off arc protection mcb when you are taking shutdown for lv board.
WE know that for Inductor X=2pifL,In DC f=0,then X=0 so,V=IX=0;But In the DC excitation of rotor of AC generator,DC motor field coil which coils are inductor so why does not applying DC voltage short the rotor coil of AC generator and field coil of motor?If it would then DC source might be damaged but it is not happened. Why does the strand conductor of Electrical power transmission line make twist?
how freewheeling diode improves the powerfactor
What are the Formula of computing Back up Time of 500kVA UPS with 4 Battery Banks, each bank composed of 43 pcs of Batteries 12V150Ah. How to compute the Back up Time of UPS? We have also 3X500kVA UPS running in Parallel same composition as I write above.
Classify driling machines.
What is FM200 Gas??Applications........