I have running 4 generator in paralel.All generators
Voltages is same(470 V),KW also same (100 KW) but only No2
generator Amper is high than another generators.
DG No:1,3,4 470V,100KW, 150 A
DG No:2 470V,100KW,400 A
Answer Posted / kj
This is caused by kvar. If the excitation is higher (field
voltage) it will take more kvar. This will only be shown by
a current not load. The KW will remain the same.
Reduce the excitation (voltage setting on the AVR) on No 2
generator until it is reading the same current as the other
3 generators.
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
How can we connect additional batteries to three phase ups? What are parameters we have to check when connecting?
Define corner frequency?
how to calculate insulation level of transformer?
I HAVE BEEN SELECTED FOR APGENCO A.E(ELECTRICAL) 2008.HOW MUCH WEIGHTAGE FOR INTERVIEW AND WRITTEN TEST.HOW I HAVE TO PREPARE. PLEASE GIVE INFORMATION IF U KNOW.WHAT ABT G.D THIS TIME.CALL RATIO 1:2
What is the phase relationship between the primary and secondary voltages of a transformer?
CPC cable .PVC \1C....I want to get sure that type is flexible indoor or to be install on trench. please advice .thanx :)
Why does curving the pole faces in a dc machine contributes to a smoother dc output voltage from it?
1hp= how much rpm
63MVA,220KV/6.9KV Transformer LV side neutral is connected to Earth pit through NGR. Whether this earth pit required to connect with near by below grouding earth mat or it is to be kept separate?
Explain the operation carried out in thermal power stations?
Why power genaration in India is at 50HZ while America its 60HZ
What is open delta Xformer? It's adavntages & Use?
When the relative speed between the magnetic fields of stator and rotor does is zero under steady state operation?
what is the necessity of under ground cables ??
In case of HV test on medium voltage cables, BS is asking for 4 U0 where as IEC is asking for 3.5 U0. Can any one advise me how this 3.5 times or 4 times U0 is derived?