I have running 4 generator in paralel.All generators
Voltages is same(470 V),KW also same (100 KW) but only No2
generator Amper is high than another generators.
DG No:1,3,4 470V,100KW, 150 A
DG No:2 470V,100KW,400 A

Answer Posted / kj

This is caused by kvar. If the excitation is higher (field
voltage) it will take more kvar. This will only be shown by
a current not load. The KW will remain the same.
Reduce the excitation (voltage setting on the AVR) on No 2
generator until it is reading the same current as the other
3 generators.

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how can i reduce sparking without stepdowning the voltage

2090


What is the ratio of Booster transformer?

1657


What is meant by bus bar protection?

647


how to calculate kvar in Akiva

1478


if i am in front of transmission line how to know that current direction without any equipment

1265






What will be the current if the resistance total in a series circuit doubles?

702


full form of electrical?

2298


my UPS suddenly goes off and all panel light also blow off.This happens even main electric supply is not interrupted.After some time it automatically starts functioning normally.Batteries are new.

1571


what is the differencce inn series and cascade connection??

4246


What is the difference between a Root Locus plot and a Bode plot?

787


which is chemical used as in ro water what is difference betweeen multi grade filter&dual media filter

1644


WHY IL=IPH IN STAR AND WHY IPH=IL/1.732 IN DELTA? WHAT IS REASON BEHIND IT?

5597


hi friend i am going too attend for hpcl in this month please help me by sending written test question papers i am in the stream of E.E.E

1537


What is an order of a system.

731


is it possible for different brand of H.V transformers to run or operate in parallel to each other? if so how much disturbance can this affact the H.V bus bar?

1649