Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I have running 4 generator in paralel.All generators
Voltages is same(470 V),KW also same (100 KW) but only No2
generator Amper is high than another generators.
DG No:1,3,4 470V,100KW, 150 A
DG No:2 470V,100KW,400 A

Answer Posted / kj

This is caused by kvar. If the excitation is higher (field
voltage) it will take more kvar. This will only be shown by
a current not load. The KW will remain the same.
Reduce the excitation (voltage setting on the AVR) on No 2
generator until it is reading the same current as the other
3 generators.

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

when the Transmission and Distribution network where is the "feeder" lines are located? and why should be used in T&D network.....

1761


what is the formula for hv test for cable and circuit breaker..????

2032


Which do you think is the most significant cause of energy loss in a factory?

2235


how to find the voltage's of a transmission line plzz help with pictures i am not able to understand

1354


Define pole pitch?

1082


How DC earth leakage currents can be reduced ?

1918


Please explain, how to test vector group of tranformer(Delta y1) . Thank

1691


how to carried out tan delta test in 11 KV alternator ?

3067


How to choose size of the cable w.r.to current carrying capacity ...

2198


Y phase plates are used in transmission line??? what is there need???

2915


How much minimum insulation required between 11kv/3.3kv transformer windings?

2427


where reactive power is used

2044


Starting Time of LT & HT Motor

1945


What is method of calculating the fault current for a MDB, 50KW, 3PH, 415V, 50HZ?

2139


12.5 tons a/c is their how much kva generator can recommend to the customer.

2022