If genrator not build up voltage , How u can Manually
Excite ?
Answer Posted / kj
This is usually done by flashing the alternator. Turn of
load first.
Disconnect the AVR and connect the battery (9-12 volts)
across the field. Must be same polarity as the AVR. Run
generator and check output voltage. Voltage will usually be
higher then normal. if no voltage or unbalanced voltage the
windings or rotating diodes are faulty.
Stop generator and disconnect battery and reconnect AVR.
Try starting generator set again and check if voltage
present. If still not working replace AVR and try again.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
71ohm,111ohm,95ohm,179ohm in calculate the total ohm in series circuit
1.why should we connect the measuring instruments in l.v side in short circuit test of a transformer? 2.why the power factor is less in open circuit test of a transformer?
Mr. mohh sahid m not satisfied for ur answer to the que weather the size of transformer increases or decreases withchange in fr for more detail go to the answer given by me
all the technical question with answers pleas send your email id ramar_eee@yahoo.com
how to calculate cooling requirement of datacentre from electrical load?
i have to install a HT panel, what components, I have to use in this and what will the diagram of that diagram,please tell me each and everything.
What is nyquist contour?
what is the difference between ac motor and dc generator
There are Two questions about Steam Turbine Generator... What is HRSG bypass of LP, HP used for in power generation? In particualar, in the event that fault of HP bypass, there would be STG TRIP in operation but none on the LP bypass fault...what's the reason ?
when the time of backcharging the transformer three phases only enough or three phase with neutral is must.from these which one is the best one.
how does WTI work ?
How to Decide(calculate) Bush bar size for copper and aluminiam ?
what is upper impedance and lower impedance of a distance relay
what is x'mer ,isolation x'mer & yltra-isolation x'mer?????
How can we calculate the KVA rating of a Distribution transformer from its core details?