Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

If genrator not build up voltage , How u can Manually
Excite ?

Answer Posted / kj

This is usually done by flashing the alternator. Turn of
load first.
Disconnect the AVR and connect the battery (9-12 volts)
across the field. Must be same polarity as the AVR. Run
generator and check output voltage. Voltage will usually be
higher then normal. if no voltage or unbalanced voltage the
windings or rotating diodes are faulty.
Stop generator and disconnect battery and reconnect AVR.
Try starting generator set again and check if voltage
present. If still not working replace AVR and try again.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the implications when 600 hp motor is started when the unit is running with Transformer of capacity 1500 KVA and DG set of 1000kva

2153


at work we have a 3 phase motor but on testing one phase isnt getting a reading. it runs 24 hours a day all week. stops and starts well no noise or heating. the phase isnt down to earth.is it just a bad meter reading or not? phases one and three came up with a resistance reading of 0.4 but phase 2 couldnt get anything shows up as open circuit.

1610


how to calculate the cable current ratingand and how much of distance the rating will be ok will the distance is incresed what the action we take

2069


in cvt,there are two windings,1a,1n and 2a,2n.in my one project i use only one winding i.e.1a,1n. the other winding is not in use, so i connect it in open delta and want to close it by ibsertibg thermal resistor. the output of cvt is 132kv/115/sqrt3. plesae tell me exact value of resistor, so i may close it to avoid the resonance phenomenin. send me answer on this email adress please. aetcon-po@aetcon.com

2783


How many devices can be connected in one zone of FACP

2270


hi plz send me reliance placement papers..i.e electrical technical papers that have been asked in reliance test.

2908


write encoder 17 pins details? pin a;b+, pin b;w+,..pin s & t. what is the meaning of b+, w+? explain;

2101


How do i carry out or know the vector group of a Dyn1 and Dyn5 transformer

1978


Define piezo-electric effect?

1077


Can we put 3 layers of cable tray while installing tray

2355


What is mean by Sensitive Earth fault & what are the effects

4432


what is a bus post insulator? explain its application in a substation.

12514


armature winding of dc machine produce alternating emf then it convert in to dc by using commutator.But only we consider armature resistance why don't we consider inductive reactane effect?

2018


how to calculate the mesh earth network resistance in such substation, is there any recommended resistance values with references , thanks!

2278


What is the effect of positive feedback on the stability of the systems?

1049