725KW Three DG set Synchronised but DG no-1 power showing
750KW DG n0-2 power showing 500KW DG no-03 showing 500KW.
DG is Shynchronised but why this different power showing?
Answer Posted / kj
If the DG's are the same rating then the load sharing is
out of adjustment.
Load sharing can be by speed droop (see answer above) or by
load sharing controller.
Adjustment of either of these can rectify problem.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
How can we decide cable size from HT panel to Transformer? Please give you reply with some examples.
how are reversing the direction of rotation of dc motor
The 3 phase 400 hp 440 volt slip ring induction motor do not take one phase amps why ? The motor is running good condition
What is formula calculation size cable wire ?
Under wat condition statcom operates as an inductor for the transmission line?
The advantages of Magnetic flux leakage technique over Ultrasonic technique for non distructive testing of material.
What is Traction? 1KVA Alternator, How much urrent taken?
Define availability (operational)?
What tests should i carry over on a newly rewinded DC Generator with voltage rating of 38 volts and current rating of 350 amps, to certify that the machine is OK?
whate is the meaning of balance/unbalance,in stabilizers type
How much kv gas generator is needed to run 2 hp and 1 hp airconditioners, plus a refrigerator and 4 Tvs
Hello to all, Please someone can send me HPCL ELECTRICAL Engg. Sample papers to me? Its urjent....my email address is.... raviasiapacific@gmail.com
what percent do you derate your copper wire when you change from copper buss to copper wire
ult of expression 'document.FrmQF.myem
HOW TO CHECK THE VECTOR GROUP OF A TRANSFORMER YD11?