Why is it that polarization index type test is required for
MV and HV motors and not for LV motors?
Answer Posted / kj
The polarisation index is used to check the insulation of
MV and HV motors because it is more accurate. Also it
allows a lower voltage than the working voltage of the
motor to be used. In LV motors the megger test is usually
twice the working voltage. If this was used on an 11kv
motor the megger would need to be 22kv.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
What is meant by bus bar protection?
DIFFERENCE BETWEEN NORMAL TRAFO AND THRISTER TRAFO?
Is it possible to measure correct value of earth resistance & cable insulation ristance with out disconncting earth lead & both sides of cable ends? If not, any other method to measure ER & CIR with out disconneting from the system.
(In MEP services) HVAC in AC Plant room what else can we provide if the chiller is not considered?
why the colour of insultor stack , petticoat is brown. Is it has some technical reason.
Why the power factor improvement is so important in industrial loads
Explain RLC circuit?
Explain what is rated speed?
On Which Pressure PRV is operated.
Dear sirs, pls check this 4-20ma to RS485 module datasheet,pls guve me some suggestions. http://www.szsunyuan.com/sy/pro_more.asp?Productid=539 Thanks. E-mail:yunianjiang99@gmail.com
What is an alternator impedance value?
hi, in the event earth grounding is not available in a project, is there any other way to make the elcb work? fyi, i have an instant water heater (6.5kw) installed, however if there is grounding in the heating element inside the heater assembly, i will get grounded. thank you in advance to those who will answer my question.
What is the formula for selecting the cabels according to load? How to calculate what sq.mm cabel to be used?
at what rate the micro controller increment its timer....is it 1micro seconds or 1/(12*10^6) seconds
What is electrical diversity factor in electrical installations?