Why is it that polarization index type test is required for
MV and HV motors and not for LV motors?
Answer Posted / kj
The polarisation index is used to check the insulation of
MV and HV motors because it is more accurate. Also it
allows a lower voltage than the working voltage of the
motor to be used. In LV motors the megger test is usually
twice the working voltage. If this was used on an 11kv
motor the megger would need to be 22kv.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
Dears we deal in Chemical are Plate earthing. Kindly call if any requirement and questions. Tech Earth Solutions Mohit Verma 8791071007
A 1F capacitor is charged to 100V initially. A 1H inductor is connected accros the capacitor througha a switch. The current in the circiut when the switch is closed is____
excitation limit of an excitor
what is the principle of operation of tungstun bulb ??
how to calculate the change over time for star delta starter for different KW motor?
can we use engine degreaser for electrical motors?
What is meaning of out of phase (making & breaking) capacity And how to calculate
What happen to the transformer if the OLTC frequently used for lower and raise occured 50times daily?
for a 400kv t/m line with 10 ampere current will corona occur?
which type of stability limit is higher,steady state or transient? why?
How shall i select the value of capacitor or inductor in a system?
i m electrical diploma holder i want to do plc $ Scada some body tell me which insitute is best for me near chandigarh
XYZ
Why is the air gap between the pole pieces and the armature kept very small?
I WANT TO know WHICH WAY IS BETTER FOR CONNECTION BETWEEN POWER TRANSFORMER AND MAIN DISTRIBUTION PANEL. 1-IS BETTER WE USE CABLE? 2-IS BETTER WE USE BUS DUCT? my transformer rate power is 2500KVA