how i meggar value of 11kv alternator winding.and with meggar.
Answer Posted / kj
See extract from service manual for HV alternator.
A 5000V motorised megger or similar instrument should be
used. Separate the three neutral leads,
ground V and W leads and megger U to ground. Repeat for V
phase with U and W grounded and W
phase with U and V grounded. Minimum acceptable limits
after 1 minute for each phase are:
New machine 300 M
In-service machine 150 M
The insulation resistance should not be less than specified
and the polarisation index should be in the
order of 2 or greater at 20 ÂșC.
(PI = IR10min / IR1min)
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
We have Diesel generator of 200KW. fuel consumption is always same,even connected light load or full load. Is it right?
how can we select the appropriate VCB ?
1.dg on load alarm/stop alarm... 2.dg on load. piu alarm alarm kaise chek krte hai
How Self works in DG set
What are diffrent type of road taxes?
what is the voltage between earth & neutral in 3 phase electrical connection.
Define closed loop control system.
why in a swquence network representation, the negetive sequence generated voltage is taken as zero?
How to calculate no of Lighning arrestors are required for protecting 50mX 50m*20m cubical building and locations of LA?
how i can calculate the size for fire cable
How we select the vector group of 3phase power transformer?
If a rotary UPS is in line through grid power; What would be the impact on Power Factor if the load through rotary ups is 25% , 50% , 75% & 100%. Will the power factor reduce with less load?
which pump used in WTP explain the function of VFD how to dtermine capacitorbank of capacity one plant
8. A DYNAMOMETER TYPE WATTMETER RESPONDS TO THE.......
can anybody sent me power grid questions. what subject should i prefer for preparation?