how i meggar value of 11kv alternator winding.and with meggar.

Answer Posted / kj

See extract from service manual for HV alternator.

A 5000V motorised megger or similar instrument should be
used. Separate the three neutral leads,
ground V and W leads and megger U to ground. Repeat for V
phase with U and W grounded and W
phase with U and V grounded. Minimum acceptable limits
after 1 minute for each phase are:
New machine 300 M
In-service machine 150 M
The insulation resistance should not be less than specified
and the polarisation index should be in the
order of 2 or greater at 20 ÂșC.
(PI = IR10min / IR1min)

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

While testing a ZCT what parameters have to check or measure?

1898


what is the minimum requirement gigaohms for the insulation test using 5kv in 300mm xlpe cable

1533


A d.c. Shunt motor is found suitable to drive fans because they require?

740


in conventional fan regulators how the current varies with speed?

1451


I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?

1504






comparision between ACB and VCB

1922


i m electrical diploma holder i want to do plc $ Scada some body tell me which insitute is best for me near chandigarh

2663


induction 3 phase motor terminal connection

2058


what is the function of Moulded case circuit breaker, why it is called Moulded?

992


Do u know any one? how to find out in motor rated amps? formula?

1546


what are carbondioxide and dcp used in fire extinguishers

1642


Define phase lag and phase lead?

647


why induction motors are rated at 0.8 power factor.

1537


sir, Is their any measuring unit of knoking? please explian?

1423


in general it is observed in power stations, the tertiary winding is used in higher rating Y-Y auto transformer but not in Y-Y power transformer. is the tertiary winding is compulsory then why it is not using in power transformer 

1302