Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

A DP Endress and Hauser flow transmitter is always tripping
pump at low flow. set point is 74 cubic meter/hr. Thorough
impulse line flushing and zero calibration has been done,
yet problem persists. What do you think is the problem and
how do you rectify this fault?

Answer Posted / carl ellis

The stated question assumes that the design criteria for a
low flow alarm SP at 74m^3/hr is valid. It is not clear
whether the problem is limited to the instrumentation
without a clear statement that the pump has been determined
to be operating properly. Since this is an instrumentation
exam, I'll assume the problem is in the instrumentation.

If the instrumentation is the problem, then the DP's
indicated DP/flow rate has to be lower than the alarm SP.
What can cause a DP transmitter to indicate a lower
DP/flowrate than it should?

If the equalizing valve is not tightly closed or leaks at
the valve seat, the DP will be lower than it should be as
the DP approaches zero, depending on the leak rate.

Damaged orifice plates read low, resulting in low indicated
DP readings.

Lower line pressure than the "design" line pressure will
reduce the indicated DP reading.

Someone changed out the orifice plate (OP)with an OP with
bigger bore or re-installed the correct OP backwards.

Since DP operation is "high side pressure minus low side
pressure equals indicated DP", a leak anywhere on the high
side will reduce the high side DP pressure and result in a
low indicated DP. That could be
- leak in the high side impulse line or its fittings
- manifold valve flange gasket leak on the high side or on
the process side
- vent leak
(however liquid leaks are usually visually evident)

In a mis-configured system, the PLC/DCS might have square
root extraction in addition to square root extraction on the
DP transmitter, which would cause a low flow rate indication
at the PLC/DCS.

Tell 'em Carl sent you.

Is This Answer Correct ?    7 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

key exchanges in wpa,wpa2,tls

1903


Calibration procedure for water rotameters

2180


why fuse block is not used for AI signal?

1874


why we should maintain neutral earth voltage below 1V while calibration? why cant it be 1.2V or 2V

2420


Derive capacitance to 4-20ma conversion formula / relation in capacitance type pressure sensor?

2222


How you calibrate absolute pressure with the calibration range of 0 to 1000 0C Absolute. Please explain the procedure for calibration.

1692


How is automatic reference junction compensation carried out in temperature recorders?

1074


what is isloted barrier how it works and what are the main purpose.how it make safe area.

2111


What is 1:1 redundancy ?

2371


How hart protocol can be connected with control valves?

1029


what is a vortex flow meter,mass flow meter and electromagnetic flow meter.particular use of this.means in which condition particular meter is used.

2216


WHAT IS MEANT BY PROJECT MANAGEMENT STRATEGIES IN INSTRUMENTATION?

3521


How to Calibrate Vortex Flow transmitter in field

1257


Exothermic reaction./ endothermic reaction

2032


sir, i preparing hpcl,ongc,barc,hal exams(instrumentation engg)pls send a placement papers

2315