1) Can anyone give me a typical value for Insulation
Resistance of 11kV xlpe cable?
2) How much will the IR value decrease per KM of cable
length added?
Answer Posted / 7anoter4
According to UL-1072 ch.57.5 insulation resistance of an
insulated conductor will be:
R=1000*K*log10(D/d)/L
D=insulated core diameter d=conductor diameter. L=cable
length.
The minimum permissible insulation resistance will be:
K=20000 Mohm/1000 ft. then L=cable length in ft. or K=6100
Mohm/km then L will be in m.
Let's say we have a 1*240 sqr.mm copper conductor 11 kV
XLPE insulated cable.
According to IEC 60502-2 [BS6622] insulation thickness=3.4
mm.
The conductor diameter is about 20 mm.
Then D=20+3.4*2=[approx.]27 mm.
R=1000*6100*log10(27/20)/m=7.95*10^5 Mohm/m or 795 Mohm/km.
Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
WHICH SIZE A.B.CABLE IS USED FOR 11KV.
how circuit breaker work.. what is the operations taking place inside a circuit breaker when an overcurrent occurs... is it similar to fuse?
plz explain the auot-reclosing circuit in electrical engineeing
any application of back emf
Why are lt windings placed near the core?
design of IGBT firing circuit for 11KV
What is the function of probe in cro?
I am about to write exam in RRB bangalore for the post of section engineer.please provide me with previous exam questions
Explain what are inter-poles and why they are required in a dc machine.
What are diffrent type of road taxes?
Why we use duplex coil and hook switch in telephone system?
Can Anyone Answer anyone of these ? Q1) why direct SOLUTION of Load Flow Studies in Not Possile ? Q2)Why majority of Buses in power system are load buses Q3)Why one of the buses in Power system is taken as reference bus (slack or swing) Bus ? Q4)Bus Admittance Matrix is a sparce (means it contains some zero elements ) matrix , give reason
what is the difference between 2 way and 4 pole selector switch???
how we sesign the transformer give some specifion regarding design of transformers
Is it possible to operate a synchronous 2-poles turbogenerator with a still-in-place faulted bar but electrically disconnected ???? If yes, should I act on the other phases as well ???