how can calibrate vacume trasmitter by HART COMMUNICATOR ?
Answer Posted / nagkon
for ex: the range is -760 to 0mmhg .
by following procedure we can calibrate the transmitter by
using hart
1.give the supply to transmitter
2: connect hart to transmitter with 250ohms series resistor
3.switch on the supply
4. hart shows device connected
5. go to process parameter and change the follwing
parameters
LRV:760mmhg
URV:0mmhg
then press send .then cross check the transmitter with
master pressure calibrator
| Is This Answer Correct ? | 11 Yes | 4 No |
Post New Answer View All Answers
What is the diffrence between ff tx and non ff tx
How to calibration a control valve?
For what reason would you possibly be compelled to make use of a Smith Predictor. Explain the idea behind the operation of this device.
What is megering????
ORP sensor working principle?
What types of Instrumentation Related Questions can an Interviewer ask in a Telephonic Interview ?
What is 3 selection available when configure the burnout protection for controller
how many types of preheaters are in cement industry & what r they can any body explain?
Give Detail information about plc,dcs,and scada system?
what is a half wave, full wave, and bridge rectifer.
how to calibrate corollaries (Mass flow meter)?
What is instrumentation measurement?
Dear Sir/Madam,im going to attend Hpcl written exams on feb 17th in instrumentation stream..can anyone send me the HPCL model papers and pattern of HPCL ....i ve not yet attended anything in HPCL...so i dont know how it comes...so just i need some model test papers and pattern ..pls help me friends...
How many interlocks at turbine side?
Explain bernoulli’s theorem. State its application.