Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calculate the earthing conductor & no. of earth pits
required

Answer Posted / sudhakar.g

The earth resistance of single rod or pipe electrode is calculated as per IS 3040:
R=100x&#961;/2×3.14xL (loge(4xL/d))
Where:
&#961; = Resistivity of soil (&#937; meter),
L = Length of electrode (cm),
D = Diameter of electrode (cm)

Example:
Calculate number of CI earthing pipe of 100mm diameter, 3 meter length. System has fault current 50KA for 1 sec and soil resistivity is 72.44 &#937;-Meters.
Current Density At The Surface of Earth Electrode (As per IS 3043):
• Max. allowable current density I = 7.57×1000/(&#8730;&#961;xt) A/m2
• Max. allowable current density = 7.57×1000/(&#8730;72.44X1) = 889.419 A/m2
• Surface area of one 100mm dia. 3 meter Pipe = 2 x 3.14 x r x L = 2 x 3.14 x 0.05 x3 = 0.942 m2
• Max. current dissipated by one Earthing Pipe = Current Density x Surface area of electrode
• Max. current dissipated by one earthing pipe = 889.419x 0.942 = 837.83 A say 838 Amps
• Number of earthing pipe required = Fault Current / Max.current dissipated by one earthing pipe.
• Number of earthing pipe required = 50000/838 = 59.66 Say 60 No’s.
• Total number of earthing pipe required = 60 No’s.
• Resistance of earthing pipe (isolated) R = 100x&#961;/2×3.14xLx(loge (4XL/d))
• Resistance of earthing pipe (isolated) R = 100×72.44 /2×3.14x300x(loge (4X300/10)) = 7.99 &#937;/Pipe
• Overall resistance of 60 no of earthing pipe = 7.99/60 = 0.133 &#937;.


If you have any doubt regarding this ...pls mail me sudhakar28485@gmail.com

Is This Answer Correct ?    4 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How select ELCB for 32amp. socket having quantity 12Nos. We have to do this wiring in PLANT. Please Also explain the incoming cable specification.

1930


-What should be minimum value of insulation resistance and maximum value of earth resistance at any electrical instillation and what is method of testing the same.

2149


What is inrush current?

1242


Why you want to join non technical field when you are an engineer?

6814


how to choose cable size with respect to load? how to convert cable size in mm2 to sq.mm?

6108


why core is useful for a transformer ?and also in its operation ?

2144


Currently what is the highest capacity (MVA) of SPPg generator available in the market?

1862


Why derivative controller is not used in control systems?

1241


Can 4pole (3 phase+neautral )RCCB proper functioning in only 3 phase load (no neautral, no Earth) ?

2199


WHAT IS THE MEANING OG (li = 7 In)

2261


Dear sir, iam completed iti ncvt electrician 2000-2002 & diploma electrical eng completed 2008-2010 distance education in rvd university, still i got B licences only but my working company want C licences, how to i get c licencese pls reply me iam in critical situation thank you karthick 9841637803

1745


How they LT panel busbar size choose

1738


Dear all: Recently we got a question about Interface between PMS and SAP-PM.once we got a update message from PMS.we should set the deletional flag for functional location in SAP system.Is there any FM or BAPI to use?There are only functional location create and change provided by SAP. Best regards!

2142


How to select a cable size for particular load?

1882


WHAT IS LOAD CELL

2196