Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

If the t/f capacity is 500KvA then what is Amps ratting of
the main breaker.

Answer Posted / athar abid

As we Know that

KVA = Sqrt 3 . Voltage(V) . Current(I)

Now for 400V (Phase-Phase) syayem

I = 500KVA/(1.732 * 400)
=500*1000/(1.732*400)
=721.7 Amps

There is no standard breaker available with this rating, so
take one step above rating i.e. 800Amps

Hope its clear.

Regards
Athar Abid

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Can anyone tell the proper diagram of star delta starter????

1914


What is pole of the system?

1124


what is meaning of sympathetic tripping with respect to relays and give the values for current carrying capacities for copper and aluminium cables from 16sq mm to 500sq mm

5066


What is mean by hot and cold loop testing?

1073


Is RTCC panel needs any control supply.

2028


Which standard we are following earthing resistance test

1391


why can the rotor of 3 phase slip ring induction motor not be a 2 phase rotor?

2045


for opening electrical shop, tips needed.

1812


What is the difference between isolators and electrical circuit breakers? What is bus-bar?

1134


Whar is the KvA rating of 33Kv substation & actual kv rating of power generaating station.

2374


What is main cause of cable's terminal point burned in Lug on high temperature although lug and cable selection is ok as per stantard and also tightness is ok as per situation. so please take in deep and tell correct answer thanku.

8253


how braking & making capacity of circuit breaker is calculated?

1985


How to connect the chemical earthing and complete process tell me plz

1849


Which test will be more severe for VCB?

2637


how to control the speed to switched reluctance motor

1925