If the t/f capacity is 500KvA then what is Amps ratting of
the main breaker.
Answer Posted / athar abid
As we Know that
KVA = Sqrt 3 . Voltage(V) . Current(I)
Now for 400V (Phase-Phase) syayem
I = 500KVA/(1.732 * 400)
=500*1000/(1.732*400)
=721.7 Amps
There is no standard breaker available with this rating, so
take one step above rating i.e. 800Amps
Hope its clear.
Regards
Athar Abid
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
how to control dc motor?
what is the IEC standard for Power Cable installation in onshore (like in direct buried ground or above groung)
What is the effect of solar radiation on the design of an Isolated Phase Busduct?
how does it help for selection of a transformer.
How does an induction motor start?
i am studying in final year can i allowed for 23rd UES of Indian army
How to findout raw or ups power? its not indicated in socket,
What is the rating of a circuit breaker needed for 300 kv load in 33KV supply line of 33/415 transformer ? Whether 800/1200 amp vaccum circuit breaker can perform for a 33 KV line in input in 415 volt in output of the transformer ?
Tell me the reason of connecting domestic t/f primary in star or delta,and also secondary side.
what is mean by transition resistance of transformer?
what is the size of cable for 15kw motor and 85 meter cable length using with vfd
our industries ht line so power fluctation(once drop of power please rectify causes
why ten delta testing is carried out on power transformer
After completing iti in electrician, how can i get certificate of electrical supervisor? What ia requirements. For it?
what is physical distance of isolator to VCB in 33/11kv sub stations