IN 500 KVA TRANSFORMER 11KV/415 VOLTS HOW TO CALCULATE THE HT
CABLE SIZE AND LT CABLE SIZE FROM TRANSFORMER TO LT PANNEL.
AND HOW MANY MAINSWITCHES OR MCBS WITH RATING ARE TO BE
PROVIDED
Answer Posted / sudhakar g
First you have to caluclate the load of the T/F i.e
KW=KVA*p.f
KW=500*0.8=400KW
I=kw*1000/1.732*415v*0.8
I=696.74 A
Based on these we can choose the Cable size ....
suppose the LT AL cable of 3.5c x 400 sqmm will give 530 A
of polycab....if we go for two runs of 400sq.mm means it is
good and the breaker size we will go for 800A ACB bresker
means it is good....
I am taking Electrical desining classes in Bangalore...It
will be usefull for designing as well as site engineers
those who are intrested to go for Electrical
Engineers....we give you indepth knowledge of Load calu,
Cable sizing, Lighting cal, panels, breaker
selection,Autocad drawing....if any body intrested means
pls call to +91-7760362623 or sudhakar28485@gmail.com
| Is This Answer Correct ? | 17 Yes | 13 No |
Post New Answer View All Answers
why ht cable end termination don't have a gland?
Hello Guys !! i want to rrb section engineer electrical(signal) previous model papers? any body help me?
why genarator genarating voltage 11 KV?
can anybody sent me power grid questions. what subject should i prefer for preparation?
there are cam operated switches - why we call cam operated , What is cam ?
How to select the earthing transformer,for DELTA TO DELTA TRANSFORMER OR ALTERNATOR SIDE.Pls post your answers and calculation.
delta motor winding resistance I take normally single winding is 2.5, which value is came delta connection ie RY ?
how we can set the IDMT relay.
What is the main use of rotary phase converter ?
i want design of D.C.MOTOR 1HP 960RPM AND 2HP 960RPM ITS URRGENT
why transformer ratings in kva? & DG ratings in kva? & Motor ratings in kw/HP?
can we synchronize star system generators with delta system generators?
What is instrumental error?
HOE WE CAN IMPROOVE BY USE OF CAPACITOR
how works inductive &capacitive sensors?