Please explain the difference between instrument range and
calibration range in terms of pressure transmitter?
line design pressure: 93 bar
operating pressure : 82 bar
press Transmitter Range?
calibration range ?
Answer Posted / ahmed helmy
- instrument range is the maximum range of instrument.
- Calibration range is at which the instrument calibrated
for example
- if we have a pressure tx instrument range 0:10 bar
- we can calibrate it at any position between 0:10 bar suppose we calibrate it at 0:4 bar its mean its calibration range
is 0:4bar and instrument range 0:10 bar
Based on your case:
- line design pressure=93 bar (max pressure in the line)
- operating pressure=82 bar
so we can install pressure tx range:0 to 120 bar and calibrate the pressure tx in range from 0 to 93 bar
Is This Answer Correct ? | 19 Yes | 6 No |
Post New Answer View All Answers
Why do you want to work here
In turbine what does term CDP, NI, NH, HSSOC means.
pls suggest suitable MOC of diaphragm for pressure measurement of UREA grade solution service fluid.
Explain about safety integrated level protection? . How it was differ from other protections ?
Explain pH, Conductivity.
what is a vortex flow meter,mass flow meter and electromagnetic flow meter.particular use of this.means in which condition particular meter is used.
what is a half wave, full wave, and bridge rectifer.
plz tell me clearly about PID.."when v have to change I value,D value,GAIN??
in differential pressure transmitter,min&max pressure range for hp&lp
i have been asked by QAFCO to appear for interview for thy post of Instrument Designer(INTOOLS)..i m engineering graduate with 5 years exp. in design engineering.Will this job profile suit me??i need all ur help n suggestions for thy same?
I m appointed as an automation trainee engineer in small firm in that I am only the one , my company give me a project on s7-200 as i m beginner I don't know how to program so please send me the helpful site so that I complete my project before deadline....please help me out in this critical situation.
How to Calibrate Level Switch in field
in valve is constructed as per SME B 16.34, then which standard is used for fire testing of valve?.
Draw a P& ID showing – orifice flange, plate, dp transmitter, isolation & bypass valves and tubing.
What are advantages and disadvantage of the ac supply load cell?