in three phase 11kv transformer (11kv/433v)
input( R,Y,B) output (X,Y,Z,N) the connection as follows
1 phase R -open
2phase y connected to both R and y of input]
3phase B- B
what is the output voltage X to N ,Y to N , Z to N
Answer Posted / pradyumna chandra panda
phase voltage ie. voltage b/w x-n. y-n and z-n is 250 volt each but line voltage b/w x to y = 0 volt y to z= 433 volt and z to x = 433 volt
| Is This Answer Correct ? | 14 Yes | 1 No |
Post New Answer View All Answers
What is the general system requirement of alternator?
When we use air circuit breaker, it has O/L protection ,time delay SC protection, Instataneous SC protection & ground fault protection. They all have some setting range. But what is the suitable/allowable setting for the above protection which will be safe for the equipment? For example-O/L protection setting have a range of (0.4,0.45,0.5,0.55,0.6,0.65,0.7,0.8,0.9,1.0)xIn Time delay SC protection have a range of (1.25,1.5,2,3,4,6,8,10,12)xIn Time delay setting is 0.02,0.1,0.2,0.3,0.4 Instataneous setting is fixed to 20xIn Gound fault setting is given 100A,300A,600A,900A,1200A This setting are for 2500A ACB. So what will be the basic allowable setting for the above protection? is there any formulae to calculate this<
Form S and "c" license application both are same? @ tneb portal
what is draiv work
I want formula to calculate current loss with distance in km.I searched many sites but didn't right answer.Plz reply me
what is stper motor
what is meant by CT`s saturation ? Can we use Metering CT`s with Protetection CT`s ?
If I bring a basic electric meter from the States and hook it up in Costa Rica in a development that has only one transformer for the 50 homes, will it still be accurate regarding the usage of kilowatt hours?
HOW TO CALCULATE CAPACITOR BANK OR HARMONIC FILTER CALCULATION
What is difference between safe PLC and normal PLC
what is p.s impedance measurement test in earthing transformer?
What is the basic principal, by which DC voltage level is increased more than the supplied AC voltage during conversion. As upto AC level it is contorrled by firing anlge but after maximum level how is it possible.Please clear picture. OR we have to supply the higher level AC?
In Air circuit breaker LSIG protection unit is used. Without fault in cables (2 runs 3Cx150Sq.mm Copper, 1Kv grade, XPLE armored cable IR value is more than 550Mohm @ 500V Megger) and load section Long time Overcurrent protection is triggers and trips the unit. We changed LSIG protection with new factory tested unit. Even then fault is persisting. Please suggest the possible causes
how we can do the insulation on secondary of ct explain and so that tan delta will within limit
How to know th details about an electrical Drawing ? Please mention the easy method.