In Transformer testing at Shop test we normally test for
vector group, open ckt.,short ckt. but what are the other
test performed for transformer once it reaches at site.For
e.g:if the transformer is dry having rating 1000KVA?
Answer Posted / guest
1. Insulation Resistance Measurement
a . For LT systems, use only 500V or 1000V Megger
b. For MV & HV systems, use 2500V or 5000V Megger
c. Remove Earth from Transformer neutral
2. Winding Resistance Measurement
R-N AND r-n
Y-N y-n
B-N b-n
3. Magnetic Current Test
Applied Voltage : RY YB BR
Measured Current : R Y B
4. Magnetic Balance Test
5. Vector Group Confirmation.
6 . Short Circuit Test and Differential Stability.
7 . REF Stability Test
8. Cooler Circuits.
9. Auxilliary Protection Circuits
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
what is ATS & RING MAIN UNIT in Distribution System?And its Function.
Briefly define and explain the following different types of Pulse Amplitude Modulation (PAM) with some examples. i) 2-PAM ii) 4-PAM iii) 8-PAM iv) 16-PAM v) Quadrature Amplitude Modulation (QAM)
What do you mean by a phase angel of instrument transformer?
how to calculate regulation constants for over head lines? and what are the regulation constant for raccoon conductor at different voltage level and different P.F?
DG Earth Value?
What is the important precuations need tocarried out while working with Electrolite in Battery PM?
how to discharge 3 phase power factor correction capacitors
can u give me a brief idea about power line carrier communication ??
Is MEN and RCD related to each other ?? IF yes then how??
How to run a three phase motor into single phase........
how you configure motorvision relay (L&T make)from DCS
What are the special cables required for explosion proof wiring?
Mention the methods for starting an induction motor?
i m electrical diploma holder i want to do plc $ Scada some body tell me which insitute is best for me near chandigarh
I WANT TO know WHICH WAY IS BETTER FOR CONNECTION BETWEEN POWER TRANSFORMER AND MAIN DISTRIBUTION PANEL. 1-IS BETTER WE USE CABLE? 2-IS BETTER WE USE BUS DUCT? my transformer rate power is 2500KVA