Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Write the formula for Fault MVA, Fault current, Base MVA.

Answer Posted / mak

The fault current of a power transformer will depend on the following;
Transformer Rating (in KVA/MVA)
per unit impedence of the transformer (%p.u.)
line/phase Voltage (VL/VP)
the following formula can be used to find the fault current on the secondary side of a transformer
Fault Current = Transformer Rating /(per unit impedance x phase voltage)

The Values of Transformer Rating, per unit impedance & phase/line voltage will usually be mentioned on the transformer rating plate / data sheet
As an example a 500kVA, 11kV/400V/3-Phase/50Hz transformer with 5% p.u impendence will have the following fault levels on the secondary side

Fault level = 500/(5%)=10000kVA


Fault current = 500/(5% x 400 x 1.732) = 14.4 kA

Remember to use 3phase voltage!

Is This Answer Correct ?    3 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Explain Continuous and Discrete signals?

1713


According to conduit size which size wiring & how many wires can we provide wires in conduit & how can we select conduit size accordingly?

1879


Why 15Amp. MCB is suitable to carry load of 1.5Ton Ac please Explain?

2149


which book to refer in electrical engineering for iocl exam & which book for general english.

2220


what r PID controllers?why they r used?what is there purpose?plz Explain in detail

2054


what will be d.g. capacity to cater together for 14hp A.C. load & 3kw lighting load

1978


what is the difference between unarmoured & Flexible cable? How to identified?

6185


what kind of quetions will ask in BHEL in interview? Plz help me?

2093


why we are not giving the zone 1 trip command to the master trip relay

1716


how can i find cable size from current rating?

1747


what is the use of the puls transformer in UPS & how it works???????????

2199


CBCT selection

2265


What is the practical way to calculate the cable size for known ampere load?

1422


Both generator parallel condition shared load equally but one genrator taking ampere more than the other what are all the causes to make like this

1727


What will happend if given Vfd out put to step up transformer

1793