Answer Posted / savarkarshriram
If cable is rated for 1.1KV the megger test( Insulation
resistance test) is done with use of 500V or 1000V.
The test probes are connected across each phase , neutral
and ground terminal so that it covers all combinations.
If it is HT cable then 2000V IR tester is used. with the
same method as explained above.
Thumb rule for minimum value is 1M ohm per KV of rated
volatge of equipment
( Mind you megger is name of company and not name of test
so engineers should use term insulation resistance rather
than megger)
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
why high speed tripping relay will be used in tripping circuit why not normal relay
What is the formulae of Megger value for a A.C.Motor
Why can't we take NO LOAD TRIAL of motors having V1 mounting??
In constant power region of 3-phase IM torque-speed characteristics, if frequency increases slip A does not alter B decreases C increases D none of above
upto how much low RPM we will run the commercial motor which is run through VFD without any problem occurs in motor.Motor rating Duty is S1 & RPM is 1400.
r we are using in gas turbine mark (5) frame (6) (made in india Bhel 1997) Ā
what is draiv work
What happen when change order of CT in GIS feeder?
PLZ sent the previous year question paper for GET in NHPC on my EMail id ppshanker@gmail.com
if 2 coil of 1000W connect in series and 200 v is applied across it . then what is the total power of coil when coil have only resistive load .
What is the formula formula for Busbar sizing and what are the things to be consider for Busbar Calculation?
What is the effect of positive feedback on the stability of the systems?
for a 400kv t/m line with 10 ampere current will corona occur?
What is a surge supressor why its is used in synchronous generators
what are the problems that generally occur in power flows??