Answer Posted / savarkarshriram
If cable is rated for 1.1KV the megger test( Insulation
resistance test) is done with use of 500V or 1000V.
The test probes are connected across each phase , neutral
and ground terminal so that it covers all combinations.
If it is HT cable then 2000V IR tester is used. with the
same method as explained above.
Thumb rule for minimum value is 1M ohm per KV of rated
volatge of equipment
( Mind you megger is name of company and not name of test
so engineers should use term insulation resistance rather
than megger)
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
ROC converges if poles and zeros lie inside a. Origion b. Z=1
wow to calculate the transformer rating(KVA)
why Current is lead 90 degree and voltage is lag 90 degree in a capacitor.? why Current is lag 90 degree and voltage is lead 90 degree in an inductor.?
Mention the disadvantages of low power factor? How can it be improved?
How many kw will suply from one db
What does the kvar means?
what is the interrelation between voltage current torgue speed and magnetic flux in case of different types of electric motors
How seriving & testing of the HT & LT breakers are done. What are the standard Ir values on which we can come to know the test is passed or failed?
I want to replace the 3 KW DC motor with AC motor so what should be the rating of AC motor? Details Of DC motor to be changed with AC are - Kw - 3, Vf - 310, If - 0.15, Va - 400, Ia - 13, RPM - 2400
How to decide the size of the capacitor for a single phase induction motor say 2 HP ??
why the active power flow of some line is increased when the active power of out is cut ?
Pls mail me utility & Dg related question with answer
whatare the disadvantages occur,if the form factor of transmission will not be equal to 1.11
In Plumbing services What are accessories we consider for a bathroom?
Installation resistance for whole installation of 16 kva & 25 KVA DTRA a) Between each conductor b) between conductor to earth c) installation resistance for each apparatus, each conductor to earth d) earth resistance for the system of earthing