Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the difference between Ith & Iu rating in MCCB.
Particularly on SACE ABB Circuit Breaker?

Answer Posted / mazed

CCB Ith & Ir Acronym Meaning
05/02/2010 9:16 AM

We are planning to replace our Chiller with bigger capacity.

The motor rating of old chiller is 375 kw whhle the new one
is 570 kw, all at 380 volts, 3phase , 60 hz. The suppllier
required us to a circuit breaker with minimum ampacity of
911 amps.

our existing Circuit Breaker is SACE ABB, Iu =1250, Ue =660
Volts, 3 poles. Their is a rating of Ith @ 45 deg C of 800
Amps maximum and Ir = 6300 max. My questions are:1. What is
the Ith & Ir means. 2. Can i use ourold MCCB with the rating
of 1250 Amps Iu?

Please all extert here help me.

My best regards to all.
Reply
Interested in this topic? By joining CR4 you can "subscribe" to
this discussion and receive notification when new comments
are added.
Join CR4, The Engineer's Place for News and Discussion!
Comments rated to be Good Answers:
These comments received enough positive ratings to make them
"good answers".

* #4 "Re: What is the Ith & Ir at MCCB stand for?" by
JRaef on 05/02/2010 7:01 PM (score 5)

Tornado
Guru
[Tornado's Picture]
Technical Fields - Technical Writing - New Member
Engineering Fields - Piping Design Engineering - New Member

Join Date: May 2009
Location: Ketchikan, AK, USA
Posts: 11914
Good Answers: 421
[Click to collapse or expand]
#1
[Comment] Re: What is the Ith & Ir at MCCB stand for?
05/02/2010 2:42 PM

Ith is the thermal current rating of the breaker. The more
the motor current exceeds this, the quicker the breaker will
trip. I'm unsure of the other abbreviations, but they may
represent the magnetic trip rating, which is nominally
instantaneous.

If the motor requires 911 A, it is likely to trip this
breaker either 1) right away if the starting current exceeds
6300 A, or 2) in a short time if the running current exceeds
800 A. So I don't think this combination will work.
__________________
In vino veritas; in cervisia carmen; in aqua E. coli.
Reply
Dalton
Associate

Join Date: Nov 2009
Posts: 28
[Click to collapse or expand]
#2
In reply to #1
[Comment] Re: What is the Ith & Ir at MCCB stand for?
05/02/2010 2:59 PM

Thanks, but how about the Iu (1250 Amps) which i believed is
the nominal current rating. Our MCCB rating Iu = 1250 Amps &
Ue is 660 volts. then their is anothr rating which is Ith =
800 max @ 45 Deg C. any idea on this Sir?
Reply
Tornado
Guru
[Tornado's Picture]
Technical Fields - Technical Writing - New Member
Engineering Fields - Piping Design Engineering - New Member

Join Date: May 2009
Location: Ketchikan, AK, USA
Posts: 11914
Good Answers: 421
[Click to collapse or expand]
#3
In reply to #2
[Comment] Re: What is the Ith & Ir at MCCB stand for?
05/02/2010 4:15 PM

My idea on that is exactly as before. If the thermal rating
Ith of 800 A is exceeded by the 911 A motor, the breaker
will trip (sooner or later).

However, if the ambient temperature at the breaker is less
than 45°C, the Ith will be somewhat higher. This may get you
by, but it looks really borderline. Reduced-voltage and
unloaded starting will also help.
__________________
In vino veritas; in cervisia carmen; in aqua E. coli.
Reply
Anonymous Poster
[Click to collapse or expand]
#5
In reply to #2
[Comment] Re: What is the Ith & Ir at MCCB stand for?
05/03/2010 5:16 AM

ASK ABB for their catalogue on MCCBs select yourself you
will find all inputs required you could download the
catalogue from ABB web site.

good luck

murali

Ex power user
Reply
Dalton
Associate

Join Date: Nov 2009
Posts: 28
[Click to collapse or expand]
#6
In reply to #5
[Comment] Re: What is the Ith & Ir at MCCB stand for?
05/03/2010 8:46 AM

thanks. this an old model MCCB from ABB. SACE SN1250 model.
Installed last 1986 by the German Contractors here in KSA.

All I want to know is if could still use this MCCB. But i
think the best solution now is to buy a new MCCB.

Rgards to all.
Reply
[Rated a 'Good Answer' with a score of 5] 5
JRaef
Guru
[JRaef's Picture]
United States - Member - New Member Engineering Fields -
Power Engineering - New Member

Join Date: Sep 2006
Location: California, USA, where the Godless live next door
to God.
Posts: 3209
Good Answers: 419
[Click to collapse or expand]
#4
[Comment] Re: What is the Ith & Ir at MCCB stand for?
05/02/2010 7:01 PM

Extract form appendix K of standard IEC 60947 -2

Voltage

* Ue = Rated operational voltage
* Ui = Rated insulation voltage
* Uimp = Rated impulse withstand voltage

Current

* In = Rated current
* Ith = Conventional free –air thermal current
* Ithe = Conventional enclosed thermal current

Short -Circuit

* Icm = Rated short circuit making capacity
* Icu = Rated ultimate short circuit breaking capacity
* Ics = Rated service short circuit breaking capacity
* Icw = Rated short time withstand current

Trip unit

* Ir = Adjustable overload setting current
* 1.05xIr = Conventional non –tripping current
* 1.30xIr = Conventional tripping current
* Isd = Short time delay tripping setting current
* Ii = Instantaneous tripping setting current

__________________

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Can anyone explain me about the capacitor calculation

2205


How to design a Unit auxiliary transformer for a power house having a unit of 65 MW and Generating voltage of 11 KV and Secondary voltage of 433V

2139


What is the reason for using a GE G101 MCB in place of an EP102 MCB if both are capable of AC circuit protection?

2658


we use capister for power factor. when we use capaciter in dg circuit  than defect dg. can we use capaciter bank for dg circuit

1933


how wecalculate breaking capcity of acb mcb mccb .explain with example

1945


gas turbine genrator reactances

2008


What is d main advantage of using double circuit 3 phase transmission ?

1941


ITI r/tv trade APPLY (J.T.O VACANCEY) ALSO INCLUD AITT ELECTRONIC,WRITEEN XAM DONE 23.03.10 BUT NO RESPONCE WHY ANATHER ID gopal_gh007@rediffmail.com

3417


Diagram and details of polarity test for Current Transformer 11kv 400/200/100/1A

3037


What is the difference between diode and a transistor in terms of the direction of current flow?

2219


why the India electrical supply transmission loss is high when compare to us

1989


what the Microsoft .NET framework is?

2012


For a spring controlled governer the relation F = ar+b (F is the controlling force, r is the radius of rotation a and b are constants), indicates that the governer is

1231


primery try cell?

2209


why they were using TRIAC instead relay in some controllers and what is the advantages.

2034