what is the difference between Ith & Iu rating in MCCB.
Particularly on SACE ABB Circuit Breaker?
Answer Posted / mazed
CCB Ith & Ir Acronym Meaning
05/02/2010 9:16 AM
We are planning to replace our Chiller with bigger capacity.
The motor rating of old chiller is 375 kw whhle the new one
is 570 kw, all at 380 volts, 3phase , 60 hz. The suppllier
required us to a circuit breaker with minimum ampacity of
911 amps.
our existing Circuit Breaker is SACE ABB, Iu =1250, Ue =660
Volts, 3 poles. Their is a rating of Ith @ 45 deg C of 800
Amps maximum and Ir = 6300 max. My questions are:1. What is
the Ith & Ir means. 2. Can i use ourold MCCB with the rating
of 1250 Amps Iu?
Please all extert here help me.
My best regards to all.
Reply
Interested in this topic? By joining CR4 you can "subscribe" to
this discussion and receive notification when new comments
are added.
Join CR4, The Engineer's Place for News and Discussion!
Comments rated to be Good Answers:
These comments received enough positive ratings to make them
"good answers".
* #4 "Re: What is the Ith & Ir at MCCB stand for?" by
JRaef on 05/02/2010 7:01 PM (score 5)
Tornado
Guru
[Tornado's Picture]
Technical Fields - Technical Writing - New Member
Engineering Fields - Piping Design Engineering - New Member
Join Date: May 2009
Location: Ketchikan, AK, USA
Posts: 11914
Good Answers: 421
[Click to collapse or expand]
#1
[Comment] Re: What is the Ith & Ir at MCCB stand for?
05/02/2010 2:42 PM
Ith is the thermal current rating of the breaker. The more
the motor current exceeds this, the quicker the breaker will
trip. I'm unsure of the other abbreviations, but they may
represent the magnetic trip rating, which is nominally
instantaneous.
If the motor requires 911 A, it is likely to trip this
breaker either 1) right away if the starting current exceeds
6300 A, or 2) in a short time if the running current exceeds
800 A. So I don't think this combination will work.
__________________
In vino veritas; in cervisia carmen; in aqua E. coli.
Reply
Dalton
Associate
Join Date: Nov 2009
Posts: 28
[Click to collapse or expand]
#2
In reply to #1
[Comment] Re: What is the Ith & Ir at MCCB stand for?
05/02/2010 2:59 PM
Thanks, but how about the Iu (1250 Amps) which i believed is
the nominal current rating. Our MCCB rating Iu = 1250 Amps &
Ue is 660 volts. then their is anothr rating which is Ith =
800 max @ 45 Deg C. any idea on this Sir?
Reply
Tornado
Guru
[Tornado's Picture]
Technical Fields - Technical Writing - New Member
Engineering Fields - Piping Design Engineering - New Member
Join Date: May 2009
Location: Ketchikan, AK, USA
Posts: 11914
Good Answers: 421
[Click to collapse or expand]
#3
In reply to #2
[Comment] Re: What is the Ith & Ir at MCCB stand for?
05/02/2010 4:15 PM
My idea on that is exactly as before. If the thermal rating
Ith of 800 A is exceeded by the 911 A motor, the breaker
will trip (sooner or later).
However, if the ambient temperature at the breaker is less
than 45°C, the Ith will be somewhat higher. This may get you
by, but it looks really borderline. Reduced-voltage and
unloaded starting will also help.
__________________
In vino veritas; in cervisia carmen; in aqua E. coli.
Reply
Anonymous Poster
[Click to collapse or expand]
#5
In reply to #2
[Comment] Re: What is the Ith & Ir at MCCB stand for?
05/03/2010 5:16 AM
ASK ABB for their catalogue on MCCBs select yourself you
will find all inputs required you could download the
catalogue from ABB web site.
good luck
murali
Ex power user
Reply
Dalton
Associate
Join Date: Nov 2009
Posts: 28
[Click to collapse or expand]
#6
In reply to #5
[Comment] Re: What is the Ith & Ir at MCCB stand for?
05/03/2010 8:46 AM
thanks. this an old model MCCB from ABB. SACE SN1250 model.
Installed last 1986 by the German Contractors here in KSA.
All I want to know is if could still use this MCCB. But i
think the best solution now is to buy a new MCCB.
Rgards to all.
Reply
[Rated a 'Good Answer' with a score of 5] 5
JRaef
Guru
[JRaef's Picture]
United States - Member - New Member Engineering Fields -
Power Engineering - New Member
Join Date: Sep 2006
Location: California, USA, where the Godless live next door
to God.
Posts: 3209
Good Answers: 419
[Click to collapse or expand]
#4
[Comment] Re: What is the Ith & Ir at MCCB stand for?
05/02/2010 7:01 PM
Extract form appendix K of standard IEC 60947 -2
Voltage
* Ue = Rated operational voltage
* Ui = Rated insulation voltage
* Uimp = Rated impulse withstand voltage
Current
* In = Rated current
* Ith = Conventional free –air thermal current
* Ithe = Conventional enclosed thermal current
Short -Circuit
* Icm = Rated short circuit making capacity
* Icu = Rated ultimate short circuit breaking capacity
* Ics = Rated service short circuit breaking capacity
* Icw = Rated short time withstand current
Trip unit
* Ir = Adjustable overload setting current
* 1.05xIr = Conventional non –tripping current
* 1.30xIr = Conventional tripping current
* Isd = Short time delay tripping setting current
* Ii = Instantaneous tripping setting current
__________________
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Explain the role of a car driver as one of a feedback mechanism.
Saving in copper achieved by converting a 2 winding transformer in to an auto transformer is determined by A voltage transformation ratio B load on secondary C quality of core material D size of transformer core
What is fault clearing time for Current Limiting Moulded Case Circuit Breaker?.
typically in power distribution substation. 1- Any idea how would be the graph of capacitor bank consumption verses time through the day . 2- How is the switching ( on and off ) of the capacitor bank, per need?
Sir 33kva 2 transformer load 900 amp calc 1800 amp mana jayega
what is mind in cable
how to do the ductor test?
How delta connection in the primary of distribution transformer reduces harmonics?how delta connections reduces harmonics?Please answer me...Hope that question is correct.
Write a note on materials used as a fuse element.
i have total 8 dg sets for synchronizing and 2 buscoupler,1 sectoin dg no 1,2,3,and 2 sectoin dg no 4,5,6,and last section dg no 7,8 ....if buscupler no 1 and 2 is off mode ..than dg no 1,2,3,will synchroniz of another dg sets?
how to calculate the step resistance for slipring induction motor,how you deside the no of step for that?
How to calculate phase to phase difference ?
Explain in brief description about the operation of DG sets.
what are the different methods for the starting of a synchronous motor.
Can u Explain about the electronic trivector meter and the use of data converters in them?