Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why we use to transmit the power in three phases intead of
single phase ?

Answer Posted / paul

I do not think the previous answer is correct. Three phase is more efficient (Power In v Power Out) in respect to AC motors, and is also more cost economical in regards to power transmission as less copper is required for the same delivered power (given the 3 phase line voltage is taken as being he same as the equivalent single phase voltage therefore allowing the use of cable with the same voltage rating), however..

The transmission power loss (and therefor transmission efficiency) in a three phase systems is the same as in a single phase system (again, assuming same total load power and line voltage).

The previous response has omitted the fact that, even though there is no neutral wire the return current in a three phase system will be subject to I^2*R losses in the associated conductors. Taking R as the loop resistance (supply and return), a single phase system power loss can be calculated as I^2*R. For a balanced three phase system, the single phase equivalent losses will be ((I/root3)^2)*R. Therefore total losses = 3*((I/root3)^2)*R = I^2*R.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is th basic difference between a d latch time line and a d flip flop time line???

2033


how works inductive &capacitive sensors?

2040


How to Calculate The sag of OPGW in Transmission Line???

3175


How much current will a 5 HP delta connected motor at no load will take?Is tat need a starter

7858


A parallel flow heat exchanger will perform better than a counter flow heat exchanger. State if the statement is true or false.

1319


What is difference between Over Current & Earth Fault protection?

2489


what is the responsibility of C license holder in industry?

9221


What is the problem of internal failure in ship engine telegraph system norcontrol?

2483


What are the advantages & disadvantages of a group electrive drive?

2203


A cable with concentric PE conductor must be used with frequency converter circuits what does its means.?

1622


For R-L or R-C ckt,time constant formula is L/R and RC respectively and its unit is in sec.Pls tell me the derivation

3350


1.why should we connect the measuring instruments in l.v side in short circuit test of a transformer? 2.why the power factor is less in open circuit test of a transformer?

2119


what r substations?what r there work?why voltages r incresed and then reduced during distribution of power

1990


What is the best thing to protect the motor from running over full current. CT or O/L or pressure transducer at the given pressure rating

1590


can anybody sent me power grid questions. what subject should i prefer for preparation?

2164