how will do square root transmitter calibration
Answer Posted / che-daniel cabardo
the formula is Q=k(square root percent of 0%,25% and so on.)
therfore k=10,constant..
for example range is 0 to 50 mmh2o
the span is 50 mmh2o.
Q=10 multiply sq. root of 25%= 50%
from the formula: %(span) + LRV
So:
0% = 0 mmh2o
25%= 25 mmh2o
50%= 35.3 mmh2o
75%= 43.30 mmh2o
100%= 50 mmh2o
| Is This Answer Correct ? | 4 Yes | 7 No |
Post New Answer View All Answers
can you provide me full detail about instrumentation in ONGC??
A flange is used for instrument connection for a system with a design temperature of 316C (600F) and a design pressure of 1000 kPa (145 psi). What is the class rating of the flange to be used for this application? Explain your answer
I have 0.75mm sq multicore cable (IS type) , can use instead of same type but 1.5 sq mm cable ? Note : The distance is around about 150 meter.
In control valve proximity inductive sensor is taken as digital feedback for full open and full close.Normally its volts 24v when the sensor acts the feed back voltage 14v so that our relay not indicating in plc panel . kindly give the solution.
Can any one tell me what type of question asked for instrumentation and control interview panel??? pls mail ramashankar.goel@gmail.com
how u choose thermowell lenght n pnumatic C/v size?
what is IEC code in cables & how to selecting cables?
what is your eligibility criteria for freashers?
How to calibrate Field bus transmitter? procedure ?
What is the Working principle of Dozing valve?
why we use impulse line of flow transmitter at 45 deg. angle both side of orifice plate.
1.what is the effect of vapour presuure in orifice plate flow measurement 2.which is more effective 2 pressure sensors or one single differential pressure sensor in orifice plate measurement 3.how to design a v/i converter and i/v converter 4.how many type of thermocouple are there 5.how many leads are there in thermocouple measurement 6.how pressure sensors are connected in level measurement in differential pressure method 7.what is the output of capacitive pressure sensor (ac or dc),how its o/p is signal charactarized 8.what is the physical meaning of discharge coeeficient,why it is calculated,orifice plate what is its value,why it is less than 1,Q at upstream is equal to or not equal to Q at downstream of orifice plate why?what is vena contracta in orifice plate 9.why rotameter is called variable area flowmeter,it can measure flow even if area is not varying,why it is made tapered 10.design a 10 bit counter ,which counter you will prefer 11.how to remove self heating error in RTD 12.which is more sensitive pt100 or pt50 13.why thermocouple are connected in parallel 14.what is lead contact error in RTD,how to avoid 15.what is P,PI,PID,PD controller,why there is no ID controller 16.what is override,split range,sequential,ratio,feedforward,cascade controller 17.why we moved from SR to JK and then JK to master slave JK flipflop,give correct reason 18.how to measure level of a closed container which contains vapour and liquid,remember no vapour gas should be leaked,so ultrasonic and capacitive is not an option,design another method 19.how to design horse race counter including sensors and signal conditioning element 20.what is bevelling
Sir, I am working as a Instrument Engineer in Grasim Industries. Can any body provide question answer for interview purpose
What types of Instrumentation Related Questions can an Interviewer ask in a Telephonic Interview ?
components of control circuit belongs to control valve