Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calculate the knee point voltage of current
transformer?

Answer Posted / puneet prashar

Knee Voltage=2X Earth Fault current(RCT + RW)/CT
Trasformation ratio

Where
RCT= CT impedeance as per manufacture1.02
RW = Wire resistance as per manufactre
say.oo32/metre then RW= 2X 200mtr X .0032

CT transformation ratio= 4000/1=4000
4000/5=800

VKnee= 2X58000(1.02+1.28)/4000 or 800 depending upon ct used

Vknee= 66.7v

Vknee> relay stability Voltage

Relay stability voltage formula will be given by relay
manufacturer as every relar manufacturer has their own formulas

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What are linear and non-linear systems?

1148


why occ characteristics curve in not tracing back when we are bringing back the rhoestat?

1915


which pump used in WTP explain the function of VFD how to dtermine capacitorbank of capacity one plant

1986


how can see the ac indoor or out door ac which Tr

2064


Can you explain about Restricited earth fault protection scheme

1909


which phase is preferred for connecting 1 phase vt used for synchronizing OHL? WHY?

2081


Please clarify, 1. Is it required to lay two runs of GI wire along with Armoured LT cable if it is laid between one big mains (63Amps TPN SDF) to small main (32A TPN SDF) with proper glanding termination? 2. If the armoured cable with proper glanding is laid from DB to CNC machine, is it required to run two runs of body earthing to the Machine from DB? 3.If the armoured cable with proper glanding is laid from Substation to Hangar, distance is approx. 100 mtrs, is it required to do earthing at shop area though the primary termination at substation is earthed through gland.

2088


WHY EARTHING NOT NEEDED IN BATTERY IN SUBSTATION

2021


i need to give section engineer (electrical engineer) for RRB. Please suggest some book

1936


what is droop control?

2257


what is the difference between fault current ant short circuit current?

2748


What is instrumental error?

1241


We have Diesel generator of 200KW. fuel consumption is always same,even connected light load or full load. Is it right?

2243


how circuit breaker work.. what is the operations taking place inside a circuit breaker when an overcurrent occurs... is it similar to fuse?

2125


Why back emf used for a dc motor? Highlight its significance.

1246