how to calculate short ckt current of trafo.
ex.3-ph 3MVA trfo. 11/440, impdence voltage=7.25%
Answer Posted / annonymous
Fault MVA = 3MVA/0.0725= 41.38MVA
So fault current on 11kV side= 41.38/(1.732x11x0.8)= 2.715kA
fault current on 0.440kV side=41.38/(1.732x.44x0.8)= 67.87kA
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
All the socket in a room become very hot, the Wall was also became very hot and the earth conductor also became live, what in your view might be the possible causes?
what is the purpose of bypass mode in energy lighting transformer?
What is Icu and Ics and what is difference b/w them. please tell me how to calculate a size of a copper bar for a system or a breaker... reply on... king.arish@gmail.com would be waiting for a logical answer.
What is q factor?
how can i get the formula to find out the cable size if i know the load of main fuse protection.
what is the circulate the diesel in DG in side pls tell parts name and picture with circulate the diesel
from generating station If 400v LT line length is 1000m how much voltage is drop and how do i calculate it? which cable will be use for this line?
What do you mean by an instrument transformer?
design a LV scheme for a 15 storied building?
Can we use BS 6651 and BS EN 62305 standards for computer room lightning ptotection in substation?
where is the need for short circuit test for 3 see is required and why? can you explain in brief with application
How phase to phase voltage comes 440V.
Why phase sequence must be same in any ht motor or generator circuit?if phase sequence doesn't same whatever will be affect on circuit?
please describe the Transformer setting, Motor setting, I/C setting, Tie setting
What is Meter MF if External CT Ratio is 150/1 , PT Ratio is 132/110 Meter CT Ratio is 200/1 & Meter PT Ratio is 110/1