Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calculate short ckt current of trafo.
ex.3-ph 3MVA trfo. 11/440, impdence voltage=7.25%

Answer Posted / annonymous

Fault MVA = 3MVA/0.0725= 41.38MVA

So fault current on 11kV side= 41.38/(1.732x11x0.8)= 2.715kA

fault current on 0.440kV side=41.38/(1.732x.44x0.8)= 67.87kA

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

All the socket in a room become very hot, the Wall was also became very hot and the earth conductor also became live, what in your view might be the possible causes?

1644


what is the purpose of bypass mode in energy lighting transformer?

2471


What is Icu and Ics and what is difference b/w them. please tell me how to calculate a size of a copper bar for a system or a breaker... reply on... king.arish@gmail.com would be waiting for a logical answer.

2441


What is q factor?

1109


how can i get the formula to find out the cable size if i know the load of main fuse protection.

1924


what is the circulate the diesel in DG in side pls tell parts name and picture with circulate the diesel

1976


from generating station If 400v LT line length is 1000m how much voltage is drop and how do i calculate it? which cable will be use for this line?

2006


What do you mean by an instrument transformer?

1057


design a LV scheme for a 15 storied building?

1930


Can we use BS 6651 and BS EN 62305 standards for computer room lightning ptotection in substation?

2236


where is the need for short circuit test for 3 see is required and why? can you explain in brief with application

1936


How phase to phase voltage comes 440V.

2069


Why phase sequence must be same in any ht motor or generator circuit?if phase sequence doesn't same whatever will be affect on circuit?

2184


please describe the Transformer setting, Motor setting, I/C setting, Tie setting

1752


What is Meter MF if External CT Ratio is 150/1 , PT Ratio is 132/110 Meter CT Ratio is 200/1 & Meter PT Ratio is 110/1

1854