how to calculate short ckt current of trafo.
ex.3-ph 3MVA trfo. 11/440, impdence voltage=7.25%
Answer Posted / annonymous
Fault MVA = 3MVA/0.0725= 41.38MVA
So fault current on 11kV side= 41.38/(1.732x11x0.8)= 2.715kA
fault current on 0.440kV side=41.38/(1.732x.44x0.8)= 67.87kA
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
If I want to connect a capacitor bank on the HT side of a 11kV/415V, 3 phase delta-star distribution transformer to supply Reactive power to it..what practical specifications of a Capacitor bank that can i've??please reply..
limitation of conductor height on ground when we consider EMC
What is the function of electron gun used in crt?
What is difference between safe PLC and normal PLC
Please provided formula for calculate the cable size from step up transformer to M.V panel, run overhead aluminum cables, total load is 5mega watt, total length 900 feet.
when the time of backcharging the transformer three phases only enough or three phase with neutral is must.from these which one is the best one.
What are the functions of different probes used in cro?
current transformer balance the power level on both sides. e.g in case of step up, at secondary side voltage rise but current decrease and vice versa in case of step down transformer. but how this power level remains same in case of current transformer and voltage transformer
what is resver in electrical enginnering with answer
In between UPS out going changer over switch and ups raising main input, both side cable gland producing heat but the cable doesn't get heat,Why?
why the neutral point in connnection oscillates?
What is meant by vector group
i karmveer bharti persuing b.tech . plz send me syllabus and name of reference books. for preparation of section eng.
How it can worked plc based electrical system And which type of software using.
Why hydropower is called renewable source of energy?