Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calculate short ckt current of trafo.
ex.3-ph 3MVA trfo. 11/440, impdence voltage=7.25%

Answer Posted / annonymous

Fault MVA = 3MVA/0.0725= 41.38MVA

So fault current on 11kV side= 41.38/(1.732x11x0.8)= 2.715kA

fault current on 0.440kV side=41.38/(1.732x.44x0.8)= 67.87kA

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Is RTCC panel needs any control supply.

2111


how to calculte capacitor range for single phase induction motors??pls tel

2170


The moisture in air will condense at

1236


any earth foult trip the relay but in welding time not trip by earth foult

3219


Difference between shunt, PMG and AREP excitation. Which is the most reliable between PMG and AREP.

9652


stand by earth fault protection (51G) for transformer rating 2000 kVA,Dyn11,33/0.400 V. LV NCT ratio and necessary resistor and metrosil values how to calculate

2866


If i am running of spindle at 2000rpm ,but How to spindle stop at the second I am resetting the machine in CNC machines

1682


how could we calculate the no of outgoings from a 800 watt distribution board

1861


In india, according to trade theory above 5 HP motor reqired star delta starter. But we R connect 11 KV motor with 14MW in Direct to line ( With VCB starter combination) Can U Guess, How it is possible ?????

2189


what is different between phase and netural

2029


1. The DC generaror,s induced output emf is connected with a DC motor(as load). when increasing the load of the motor by using brake drum or any way. what are the parameters will changes in both motor and generator(voltage, current, resistance, frequency, speed, torque, power, flux etc...) 2. Similarly for AC generator and AC motor 3. similarly if using DC batteries instead of DC generator, What happens?

2344


what is the difference b/w ATS and HTS?

2238


what is the transmission loss for electrical supply? specifically a large shopping complex where the grid is half KM away, what will the % of transmission loss? is there any transmission loss for captive unit generation for above set? thanks

2032


can we use NPT glands in LT panel

1889


How can calculate the earthing strip of Copper/GI for rating of 30kV,discharge current 10KA Lightning arrester.

2386