how to calculate short ckt current of trafo.
ex.3-ph 3MVA trfo. 11/440, impdence voltage=7.25%
Answer Posted / annonymous
Fault MVA = 3MVA/0.0725= 41.38MVA
So fault current on 11kV side= 41.38/(1.732x11x0.8)= 2.715kA
fault current on 0.440kV side=41.38/(1.732x.44x0.8)= 67.87kA
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Is RTCC panel needs any control supply.
how to calculte capacitor range for single phase induction motors??pls tel
The moisture in air will condense at
any earth foult trip the relay but in welding time not trip by earth foult
Difference between shunt, PMG and AREP excitation. Which is the most reliable between PMG and AREP.
stand by earth fault protection (51G) for transformer rating 2000 kVA,Dyn11,33/0.400 V. LV NCT ratio and necessary resistor and metrosil values how to calculate
If i am running of spindle at 2000rpm ,but How to spindle stop at the second I am resetting the machine in CNC machines
how could we calculate the no of outgoings from a 800 watt distribution board
In india, according to trade theory above 5 HP motor reqired star delta starter. But we R connect 11 KV motor with 14MW in Direct to line ( With VCB starter combination) Can U Guess, How it is possible ?????
what is different between phase and netural
1. The DC generaror,s induced output emf is connected with a DC motor(as load). when increasing the load of the motor by using brake drum or any way. what are the parameters will changes in both motor and generator(voltage, current, resistance, frequency, speed, torque, power, flux etc...) 2. Similarly for AC generator and AC motor 3. similarly if using DC batteries instead of DC generator, What happens?
what is the difference b/w ATS and HTS?
what is the transmission loss for electrical supply? specifically a large shopping complex where the grid is half KM away, what will the % of transmission loss? is there any transmission loss for captive unit generation for above set? thanks
can we use NPT glands in LT panel
How can calculate the earthing strip of Copper/GI for rating of 30kV,discharge current 10KA Lightning arrester.