If a control valve is hunting means means if we are giving
50% to the cv, the cv will open at 51% then slowly slwoly
it will reaches 49% , then it will reaches again 50%, this
type of action occured frequntly.. so what to do for solve
this problem. The possible cause is in volume booster or
positioner's relay.. positioner is double acting .. and
make siemens..sipart.The cv is double acting and mounted
for anti surge operation, it having 4 nos. volume booster,
one sov, one positioner, etc..?
Answer Posted / aftab ahmed mazari
Check the following items:
1. Any loose connection or leakage of pneumatic signal.
Check all tube fittings with soap solution.
2.Check the gland packing should not be so tight. If feel
tight, get loose them a bit.
3. Check the pneumatic relays of Postioner. Get clean its
ports, nozzle, flapper etc.
4. Also check, that linkage, feed back mechanical link
should not have any dent, grove, burs etc.
aftabmazari@yahoo.com
| Is This Answer Correct ? | 17 Yes | 0 No |
Post New Answer View All Answers
What denotes the 5/8mm in the 3300XL 5/8mm proximitor probe?
what is the minimum power (P=VI)to produce a spark?
Why are the uses 24vdc in industries
why we are using drum level control valve air to close?
What are different types of orifice plates? State their uses.
what is the procedure of belt scale calibration?
what is the importance of CV in the control valves? how it is calculated?
what is the calibration procedure for transweigh make weigh feeder?
sir, give me placement papers and interview quistion of birla group company of copper.
types of cable..? Use of every types of cable..?
i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....
when the instrument tapping on pipe line is located below and transmitter is located above the tapping point for liquid service transmitter, what should we do, is there any additional drain valve is required??
What is the difference between mmwc and mmwg?
Drum level tx with GP4 with zero elevation:7300mmh20 on HP and 8050mmh2o on LP as range but on commissioning the tx readiing is max,Why this reading?
What is instrumentation control?