If a control valve is hunting means means if we are giving
50% to the cv, the cv will open at 51% then slowly slwoly
it will reaches 49% , then it will reaches again 50%, this
type of action occured frequntly.. so what to do for solve
this problem. The possible cause is in volume booster or
positioner's relay.. positioner is double acting .. and
make siemens..sipart.The cv is double acting and mounted
for anti surge operation, it having 4 nos. volume booster,
one sov, one positioner, etc..?
Answer Posted / aftab ahmed mazari
Check the following items:
1. Any loose connection or leakage of pneumatic signal.
Check all tube fittings with soap solution.
2.Check the gland packing should not be so tight. If feel
tight, get loose them a bit.
3. Check the pneumatic relays of Postioner. Get clean its
ports, nozzle, flapper etc.
4. Also check, that linkage, feed back mechanical link
should not have any dent, grove, burs etc.
aftabmazari@yahoo.com
Is This Answer Correct ? | 17 Yes | 0 No |
Post New Answer View All Answers
I need control valve ISA hand book. Is there any site to download that big book containing all the pages. Written by Paul Friedmann
How to calibration coriolis flow meter?
what effects a surging can produce in the compressor
The Design Calculation of Level Transmitter For Different Structure open & Closed Vessel, Eg. Diff. Level Tx., Capacitance For Continous Operation
What is loop1 and loop2 in MTS LT?
explain key exchanges in all security modes WPA,WPA2,TLS?
how can i calibrate the temperatuture gauge used by temperature bath(dry block) i mean step by step procedure?
How to Calibrate Flow Switch in field
what is KV and XV valve
if my flow is 20000 m3/h than which range of DPT i have to use????
what is function of switch, and how is it work, explain with difination
Which type of pressure can be measured by these elements?
How can measure flow in oil line?which type of transmitter is generally used?
how many types of preheaters are in cement industry & what r they can any body explain?
What is the working principle of the magnetic meter?