Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

my company total load is 1000kw, 415volt, all load are
inductive load. incoming powerfactor is .8. we want to
have0.95 pf connecting capacitors. so now how much rating of
capacitors we have to connect? show how?

Answer Posted / rman

currently, the load is 0.75MVAR operating at 0.8pf. to enhance it to 0.95pf, the MVAR must be decreased to 0.329MVAR.
Q=0.75-0.329=0.36MVAR
0.36MVAR must be your operating reactive power. therefore your capacitance must be {0.36M/[0.36M/(415*0.95*sqrt(3))]^2*sqrt(3)} which will be your reactance at 0.0969 per phase. also to find the capacitor to be inserted per phase,assuming your frequency is 60Hz, C=(2*pi*60*0.0969)^(-1)
therefore the C=27.37mF

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

can the measured percentage error during calibration of single phase energy meter be negative?

2381


what are the Alarm, Trip & Safety equipment (Issues) present in Power Transformers pls Mail it to ashokbabunhce@gmail.com

1893


how pt is using

1927


Sir,In our company there are 3 caterpillar make(capacity:(1) 3.3KV,2.5MW(2)3.3KV,2.5MW & (3)3.3KV,1.9MW) & 1 deutz make (capacity:11KV,3.8MW)gas engines utilised,all are running in paralell. There are three transformer utilised,(1) 6.25MVA,3.3KV/22KV,Impedence voltage:6.7% used for two generator,both are 2.5MW(2)5.5MVA,3.3KV/22KV,Impedence voltage:7.2% used for one generator of 2.5MW & (3) 5.5MVA,11KV/22KV,Impedence voltage:7.8% used for one generator of 2.5MW.all generator breakers capacity of 1250Amps. Sir,I want the details of fault level calculation of generator,transformer individually & for whole system. If you require any information from me.feel free for contact me sir.pl.send the answer of my question as the earliest as possible.

2114


100 MVA 3-phase alternator with earthed neutral has a reactance of 5 ohms per phase. what will be the fault MVA of generator.

2342


What is EHT tariff or Power factor Tariff ????

2326


Tell me in detail about c.t. And p.t. ?

1135


what about the power of wattmeter at starting and loding?

2076


can you please send me the technical questions and aptitude questions of honeywell and jindal steel electrical engg. question paper my e-mail ID is(kkesavanraj@gmail.com)

1977


Explain few advantages of electric traction system?

1106


what is the best transformer oil breakdown voltage?

1107


Logic using 1 kV or 1,1 kV grade in house wiring Low voltage cable. Explain/suggest? some use 1kV and some prefer 1.1kV grade insulation low voltage cable why??

1623


what is meant by 2 within a star in a voltmeter dial?

2040


please describe the Transformer setting, Motor setting, I/C setting, Tie setting

1752


how to ctrl motor by use of ac or dc drive.plz explain evdintly

2021