Answer Posted / rman
its very cheap because you only need 2 transformers. but the total capacity of these 2 transformers cannot be used remembering that the rating of each transformer is multiplied by a factor of sqrt(3) which is only 1.73
i.e. two transformers rated at 50kVA to be open delta.
the total is 2(50kVA) which is 100kVA but the transformer can only carry 1.73(50kVA) which is only a total of 86.5kVA
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
how to design the heater in temperature control unit to heat 50KL of water?
How to calculate Number of Earthing Pits....???
What is quadrantal symmetry?
hr round
what is the constructional difference between a power transformer and potentian transformer?
Do Phase angle measurement have any application in freq/harmonics measurement? If so how?
Why delta star trformers are used for lighting loads?
what is thermal resistance of PVC Cable.
sir,in our plant we r using SATEC PM172E power reading meeters in HT panel side it is monitoring the MB data smart viewer(sever).but last one week we did not get readings inthe server only available in meeter.tell me how communicate meter and server. and also what steps we take for checking.
What are the advantages and disadvantages of negative feed back?
If I want to connect a capacitor bank on the HT side of a 11kV/415V, 3 phase delta-star distribution transformer to supply Reactive power to it..what practical specifications of a Capacitor bank that can i've??please reply..
how can we say that stator magnetic field rotates with synchronous speed?can we derive?
What is the difference between circuit breaker and isolator
Any one who apply for Ferro Scrap Nigam Limited cn join with me at rajuhalder@indiatimes.com or 09669717028
Can any one provide the inspection procedure of MIMIC for VFD panel? Details: If someone wants to have a mimic in the VFD panel what are inputs considered for the mimic(like on,off,trip) whether we are able to add speed variation in the mimic(if so how can we get) and what are the parameters to be checked in the MIMIC during inspection?