I am working on a 11KV system with fault current of 40KA
for 1 second. I have selected 2500MVA 11/0.433KV
transformer.
How can i find the impedance value for this transformer?
Please help me.
Answer Posted / kaushik
i don't understand the purpose of giving 1 second ......
but what i think solution will be
s.c mva=1.732*v*i.
s.c mva=1.732*11000*40000.
s.c mva=762.08 mva.
per unit impedence of the transformer will be= (base
mva)/(s.c mva)
taking transformer 2500kva(i think it is wrong 2500mva)
we get
=(2.5/762)*100=0.328% of tranformer impedence
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Write the analogous electrical elements in force voltage analogy for the elements of mechanical translational system.
What are the uses of lead compensator?
How to know the following data of synchronous generator 1. D-Axis Unsaturated Reactance 2. D-Axis Unsaturated Transient Reactance 3. D-Axis Unsaturated Sub - Transient Reactance
why any centrifugal blower draw more current in starting. consider id fan and fd fan?
Why is a synchronous motor always star connected??
how to check avr of dg set of 125kva
Minimum IR value of 1.1 kv grade 3.5c (300, 240,185,150,120,95,70,50,35,25) sqmm Aluminium XLPE cable and 4c (16, 10,6 & 4) sqmm cu arm cable between RY,YB,BR,RN,YN,BN,RE,YE,BE & NE.
why only exciting current is shown not primary current in transformer???
what is difference between earthingpits,earthing grid & earthing mess?
What is the one main difference between ups & inverter ? And electrical engineering & electronics engineering ?
how to maintain frenquncy with syncronising sub-station for distribution
What is the Diff. btw Manule Pull Station & Manule Abort Station Switches used in FM200 System??
What is the difference between the transmission line and distribution line?
what is the cause of voltage dipp or swell in the transmission lines?
Which is the largest hydropower station in the world?