I am working on a 11KV system with fault current of 40KA
for 1 second. I have selected 2500MVA 11/0.433KV
transformer.
How can i find the impedance value for this transformer?
Please help me.
Answer Posted / kaushik
i don't understand the purpose of giving 1 second ......
but what i think solution will be
s.c mva=1.732*v*i.
s.c mva=1.732*11000*40000.
s.c mva=762.08 mva.
per unit impedence of the transformer will be= (base
mva)/(s.c mva)
taking transformer 2500kva(i think it is wrong 2500mva)
we get
=(2.5/762)*100=0.328% of tranformer impedence
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is Antipumping Function & If we have C.T how we find the Ratio ?
high voltage transformer input voltage,current and amps rating..distributed transformer input voltage,current and amps rating...
What is the principle of HIGH SPEED DIRECT DRIVE MOTOR ?
how to check avr of dg set of 125kva
which IS or IEC is used for earthing,breakdown voltage of transformer oil, hv/pd testing and all type of electrical testing
In radial network the source is fed from 1 end both ends at central
WRITEDOWN FEW RELY CODES
what is the total power generation in india?
what is the prinsiple of dc motor and construction and working ,application of dc motor.
What is an iron loss or core loss pi?
State The Difference Between Generator And Alternator?
what is gridrotor resistance starter
List the advantages of star-delta starter with induction motor?
Draw a SLD for main panel for school having connected load of 1200kw and emergency generator 200kw.also show the increase of additional load of chiller 225kw in the lv panel indicating meter postion size of transformer ,cables and capacitor bank.
how to calculation increase capacitor,increase power factor for three phase.