there is a power transformer 66/11kV in delta-delta
connection has 5 feeder coming out from the secondary side.
One of the feeder in it normally loaded (loaded than other
feeder)and this feeder usually trips with double OCR causing
the bank transformer to trip. Now if the load of this feeder
is put on other transformer then that no problems occurs on
that transformer or the load. However normally all the
test(IR, PI, short ckt, open ckt,grounding test and other )
has been conducted for this but evertything transformer.....
I am not geting what is the actual problem...
Answer Posted / parin patel
This thing happened dew to %Z of transformer.lesser the %Z current supplied by transformer will be more.
example:- there are two transformer
transformer 1: 66/11 kv,%Z= 5% ,15 kVA
transformer 2: 66/11 kv,%Z= 7%, 15kVA
If load is constant(same), current supplied by transformer 1 at 11 kv is more than current supplied by transformer 2 at 11 kv.
In your case ,you have to check the value of feeder current when it's supplied by two different transformer.in both case it might be different.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is referred to the electron in the outer orbit?
CAN CU XLPE/PVC CABLE BE USED INPLACE OF LOW NOISE SCREENED CABLE? KINDLY GIVE REASONS
I am B.E.electrical engineer having 7 years of experience in Transformer testing upto 315 MVA.I want to khow how I can get the 'Electrical Valuer' License.
Benifits of 3ph 4 wire metering over 3ph 3 wire
What happened when capacitor connect series in ac circuit?
why does connected a indutor with mnsformeretering core of current transformer ?
what is the reason the main breaker is trip during the motor is running? (some time the breaker is not trip)
How would you calculate power loss in a resistor?
Can you explain about TEE protection scheme?
why chock were used in old tubelights but are not newest tubelights?
What is the actual calculation for transformer short circuit test?.
how the phase convertor changes the no. of phases
How to test the vector group of a Yd11 transformer? what are the relations to be checked between various vectors to confirm this vector group?
can we install HT panel & LT panel side by side or how much clearance is required ?
how to avoid electrical shock how capacitor store charges wat are the speed control of induction motors state faradays law flemings left hand rule what is rotary converter wat is transmission and distribution what are the sources of energy abrevation of acb,vcb,sf6,igbt what is output equation of transformer which test copper iron and iron loss are calculated what is eddy current draw a single line diagram (10 marks) draw direct online starter(10 marks)