In a running D.G set engine and Alternator is revolving at
1500RPM but no output in the terminal>>>>what to do??
someone told excitation problem ....please advice
Answer Posted / parvesh sharma
Some times the exciter will we discharge due to the leakage or reverse supply at this condition we excite the exciter of the alternator, from 24 volt DC external supply for few time than start the DG it will generate the full voltage.
Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
Why L.T.Cable voltage rating is 1.1kV,where as system voltage is 0.415kV?
Starting times for soft starter & power factor is thier any standard or datas available in manufactures list. Kindly suggest.
what is the purpose of shading ring or shading coil in electrical equipments.
What is measurement?
what is the prosses for getting of 33kv licence (i have completed my engineering degree & working in 33kv substation for contract basis )????
WHY THE RATINGS OF THE TRANSFORMER IS 33KV WHY NOT OTHER???
Is it a better option to procure screw type air compressor rather than reciprocating air compressor?If so, what is the reason?How should we select an air compressor(100 CFM)? Please mention the important parameters of air compressor.
i m electrical diploma holder i want to do plc $ Scada some body tell me which insitute is best for me near chandigarh
hi, i finished b.tech eee in 2008, im worked in dg sets mfg company , now i left job in 6months back, now again i want get job core side, how can i get? is there any couses we have learn to get better oppurtunity? /
What is the purpose of stablization resistor in high impedance bus bar protection
How to setting the volume of RTCC panel AVR (11kv) controller
Importance of fault current in power transformers and how to monitor the same? How is it different from winding temperature?
how synchronous condenser is used in place of synchronous generator with out negotiating IEEE standards? Can i use 3 generators as synchronous generators and 2 generators as a synchronous condensers in an IEEE 14 bus system with out disturbing the standards?
I Have 3 Phase 10 KW AC Alternator i found one phase weak, so what will be the reason & what action shouls i take to rectify the same.
i am completed in B.E(Electrical and Electronics Engineering) with 8 months experience in Quality Control Engineer at Bharathi Industries,Coimbatore.