Answer Posted / javed iqbal
calculating the ct ratings depend on the load either motor circuit or transformer circuit. for example if we have a motor which full load current is 160A then we need a ct 200A/1A or near.Mean that primary current is 200A and secondary current is 1A which is usually use for measuring the motor current on running condition. Because measuring instruments are design for low current inputs mean that 1A is equal to 200A and when motor running on 100A then its equal to 0.5A but measuring device configure it to 100A on display.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
what is calculation mathod/formaulla for deciding Size of busbar (Copper/ aluminum)for L.T. panel on Various Fault level like 50kA,25kA,10kA
how to design step down 12 V, 1mA small transformer from 220 V AC? Because according to VI relation and power transfer it results bulky...
For a stable system, where should the poles of a system be in a root loci plot?
What is the meaning of 40X8X2 busbar dimensions for carring load of 400 Amps
what are pilot cells
What will happened if the neutral of secondary of Xformer ( Star point) Note it's above KVA rated Xformer
can mini-curcuit supply MIL-tested transformer !
10 Mtr Hight of Lighting Arrestar how much area coverd??
What happens to voltage when current through the inductor is constant?
why do we put a transformer on soak before loading it
Why do we use center tap transformer that used with portable tools
How to calculate the phase to phase clearness of HT /// LT bus bar?????
What is the tipical Online UPS input voltage for 20 KVA load ( 3 Phase or 1 Phase )? Why ? Explain it...?
DIFFERENCE BETWEEN NORMAL TRAFO AND THRISTER TRAFO?
How to calculate multiplying factor of dc energy meter