HOW TO CALCULATE THE CAPACITOR RANGE FOR LOAD FOR PF
IMPROVEMENT?
EXPLE:FOR 65 HP LOAD HOW TO CALCULATE CAPACITOR RANGE?
Answer Posted / manish deswal
let us conside current p.f = .8 & improved to .9,
Load = 65 hp =65 * 746 = 48.49 KW
KVA1 = 48.49/.8= 60.61
KVAR = Squareroot of [ square(60.61)-square(48.49)]=36.36
KVA2 = 48.49/.9= 53.88
KVAR = Squareroot of [ square(53.88)-square(48.49)]=23.49
Increased Capacitor bank capacity = 36.36-23.49 = 12.87 KVAR
Is This Answer Correct ? | 3 Yes | 3 No |
Post New Answer View All Answers
What is dc current source? Differentiate between ideal and non ideal current sources?
In motors how many types of cooling systems were used?
71ohm,111ohm,95ohm,179ohm in calculate the total ohm in series circuit
Why we use mho Relay in long transmission line?
What is the difference between PLC and Embeded system
why we not used 11kva as a direct our electrnics component.
What is the ratio of Booster transformer?
I have 2 KW electric water heater.I am gonna use it in controlling water temp.so I needed to increase or decrease the heating capacity.is there any electrical-electronic circuit for varying the resistance & so current?
We have 90mX100m hangar with 16 no.of supporting pillar. It is required to provide power supply on all pillars. what is suggested earthing scheme for hangars.
what is the differation bewreen kwh & fundamental kwh in electronic trivector meters
sourse is 66 KV / 350 MVA, transfarmer is 1000 KVA 6.6 / 0.415 kv, iF fault is 28.75 MVA on 0.415 KV Bus then calculat the Transfarmer Impidance
what happens if dc supply is given and the remedies for it.
What is UPS and How do you maintain the UPS Maintenance? Brief Description on UPS maintenance.
pls,send the previous year written test questions.
What is Phase to Phase clearance for 800V System Operating Voltage as per IEC61439