WE ARE HAVING YOKOGAWA CENTUM CS 3000 DCS, 2 FCS AND 4 HIS "
When the operation Download to HIS message appears:
Equalize start. HIS0163
WARNING: Could not connect to equalize destination. (7001)
Retrying. Number of retries = 0/1
ERROR: LdXopsLoadMain: connect error 10060
ERROR: LdXopsLoadMain: connect error 10060
ERROR: Processing terminated due to connection error. (7002)
Equalization end with errors. HIS0163
---- ERROR = 3 WARNING = 1 ----
Tell me, please, why and how to solve the problem."
Answer Posted / prashanth
thanks mr Jigar Anadkat
Instrument Engineer
IBN RUSHD a SABIC affiliate.
your suggession really helped
actualy firewall was turned on in HIS0163.
I TURNED OFF the fire wall and gave download,then it got
dowloaded successfully.
thank you
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
in valve is constructed as per SME B 16.34, then which standard is used for fire testing of valve?.
Difference between ultra sonic flow meter
What you mean by multi stage control vavles?
What are the maximum packet size of: a) HART b) Profibus DP c)Profibus PA d) DeviceNet e) Foundation Fieldbus
what is the advantage of submersible level transmitter compare to ultrasonic level transmitter?
why Fahrenheit unit of moistur analyzer transmitter
HOW TO CHOOSE FREAQUENCY IN FMCW TYPE RADAR INSTRUMENTS. DESIGN BASIS OR DESIGN CALCULATONS ?
what is the input of digital counter during the the calibration time?
Please can anybody help for control valve sizing step by step procedure?
can you provide me full detail about instrumentation in ONGC??
How to Calibrate Ultrasonic flow Transmitter in Field
What is the right procedure for adjusting the gap voltage of bently nevada vibration sensor?
Describe a time when you anticipated potential problems and developed preventive measures.
Positioner usage.
What is the use of GMV in turbine?