plz tell me about for how many rating (for 500kva)how much
current taken?
Answer Posted / nwachukwu kelechi
The general formula for a 3-phase power transformer is
given by:
power(KVA)=1.732*V*I*pf.
therefore,depending on the pf under consideration, assuming
a unit power factor,500kva power and input voltage of
11000V we have;
current(I1)= 500KVA/(1.732*11000*1)=26.24Amps.
If the output voltage is 400V, the current will then be:
current(I2)= 500KVA/(1.732*400*1)= 721.7Amps.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
please send me the previous year's question papers of jindal GET exams
what happen as when voltage drop(or may decrease) ? in case of atomic base theory?
What is the formuala to calculate the rating of motor protection circuit breaker
WHAT IS THE DIFFERENE IN ACTION OF MCB,MCCB,RCCB
How you give clearance to a spare feeder.
What is the Current equation in series RLC circuits.
I just purchased a 4 position cam switch to be used to operate a 3-speed blower motor. The motor is a 10 amp motor and has 3 wires that are used to control speed. The cam switch was rated at 660V 20 amps but when I received it, I noticed that it has AC-15 operational current rating (Ie) of 4/5 amps. If I am reading the label correctly. the 4/5 amps is related to 440v/220V (Ue). Other ratings are AC-3: 5.5A, AC2: 7.5A and AC-4: 1.5A. My questions are 1) Is it safe to use this switch with the motor I have 2) what is the difference between the 20 amp Ith ratting and the Ie operational ratings?
What are the factor to be consider for CT selection in 132kV substation?
In Indian Household, generally we receive 220V AC single phase supply. But AC has 2 phases, +ve & -ve. So in +ve half cycle current is flowing...so what happens in the -ve half cycle?? Please illustrate.
Explain Continuous and Discrete signals?
Swg formulae
Does the motor power displayed on the Motor name plate is the mechnical power motor delivers or it is consumed power from the system?
transformer spections :: input voltage 0-110-230v; output volage 0-10-12-14v; amp=3A using CRNO CORE, capcaity=50VA primary turns = ? ; secondry turns =?
specific difference of ICT&Auto Transformer
what is DRP panels?