plz tell me about for how many rating (for 500kva)how much
current taken?
Answer Posted / nwachukwu kelechi
The general formula for a 3-phase power transformer is
given by:
power(KVA)=1.732*V*I*pf.
therefore,depending on the pf under consideration, assuming
a unit power factor,500kva power and input voltage of
11000V we have;
current(I1)= 500KVA/(1.732*11000*1)=26.24Amps.
If the output voltage is 400V, the current will then be:
current(I2)= 500KVA/(1.732*400*1)= 721.7Amps.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
What are test signals and their significance?
DESCRIBE THE CONSTRUCTION ANDOPERATION OF BELT CONVEYORS AND SCR CONVEYORS , DRAW NEAT SKETCHES
Following test should be conducted to find out relative polarity of transformenr terminals A no load test B back to back test C phasing out test D none of above
11kv/433v delta/star distribution transformer primary side full load Ht current is 83.33A in , but input side VCB rating 800A.why?
What is the Nyquist criterion regarding control systems?
one split ac how can told of this ac which Tr tell me us
can we do the star delta connection of capacitor for 3- phase motor starter.
What is the universal motor?
why power not passes in plastic and rubber material
WHAT IS counter flux IN CT?
WHAT IS THE TOTAL POWER GENERATION IN CHHATTISGARH?
Initially, when the input is not equal to the output — what type of response is this?
What do you understand by oldham's coupling ?
in a silicon diode we can measure .7v in a voltmeter.but why we can't use this voltage for using?
when measure the core loss of three phase distribution transformer or three phase reactor loss, one phase shown negative watt loss. why??