plz tell me about for how many rating (for 500kva)how much
current taken?
Answer Posted / nwachukwu kelechi
The general formula for a 3-phase power transformer is
given by:
power(KVA)=1.732*V*I*pf.
therefore,depending on the pf under consideration, assuming
a unit power factor,500kva power and input voltage of
11000V we have;
current(I1)= 500KVA/(1.732*11000*1)=26.24Amps.
If the output voltage is 400V, the current will then be:
current(I2)= 500KVA/(1.732*400*1)= 721.7Amps.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
UG cable sizes were specified in sqmm. But practically its not coming to mesure. What's the reason for that? And how they specify the size of the cable?
what is the difference between pvc & fiber glass cables
What are the functions of different probes used in cro?
What is Instantaneous Earth fault relay,how will work
The SFC of an engine is 0.25 kg/kW hr. when the fuel used has a calorific value of 36000 kJ/kg. the thermal efficiency of the engine is
What is Bolted fault?
can you any one give exact mathematical relation between AC current and DC current?
what is the difference betweem star connected motor & delta connected motor?
What we mean by vintage of an engine+Generator?
Why field rheostat is kept in minimum position while armature rheostat at maximum position?
I HAVE A 50A MCCB AS PER DESIGN LINE WIRE CONNECT UPWORD SIDE AND LOAD IS CONNECTED TO DOWNWARD SIDE TO THE MCCB.IF NOW ANY ONE CHANGE SUPPLY & LOAD(WISEVERSA) WHAT HAPPENS ? DOES MCCB OPERATION OR WORKING FUNCTION NORMAL IF YES THAN WHY THERE ARE MARKED LINE & LOAD ON MCCB.
sail kaott diploma ece ke interviw me qus.kis parkar ke aate hai aur G.S me kya puchate hai kya sameedyaan me kis parkar ke qu.puchate hai
what is the differencce inn series and cascade connection??
we have 3.5MVA-11/6KV transformer. how can we calculate earth fault current and NGR calculation?
Discribe type of fault in DOL and stardelta startor.