Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why we not use 2-20Ma or 1-20Ma

Answer Posted / j jones

Sai Kiran.c is correct is saying that we don't start from 0mA because we need a "Live Zero" this is so that if the control loop goes open circuit we have an indication of this.

why do we use 4-20mA, not 1 or 2mA - 20mA, well simply just as in a pneumatic system we use 5-15psi, (0.2-1bar) it gives us the most linear output, and above that, if we were to use 1mA, any induced voltages from eddie currents in cables running alongside could cause a mA to be produced by the resistance of the cable, so our readings would be affected, and if we amplify the signal, the amplification has to be greater as we have to amplify 1mA more than a 4mA signal

Is This Answer Correct ?    2 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to calculate P,I&D value in PID controller ?

2080


please send data bank of quetions answers on analytical instrumentation.

1816


What are different types of control valves?

1523


Somebody tell me in what way i need to prepare for csio pgrpe(adv instrum eng)interview?what all the quest can i expect?

2526


How can we use feedback signal frm rtd for monitoring and in dcs for controlling ,then which type of rtd is sutaible 2 , 3,4wire and why ?

1574


what is Best Among SINK Or SOURCE Type Design In Digital Signal, Either Iput Or Output? WHY?Can any one..

2103


what is scale factor of proximitor & unit of the vibration.

2069


I have completed B.E. Instrumentation & control in 2009. i have 3 year industrial job experience in chemical plant.now, I want to join M.E. in external. so, Plese say easiet way and good institute name.

1861


Can anybody tell me how to select the size of earthing cable for DCS & PLC system.Please tell me any relevant answer here or mail it to me.

2146


What is stripper & spilitter ? Diffrence in this.?

2436


why we are using drum level control valve air to close?

2032


what is use of communication wire in multipare cable(oil and gas field), why this communication wire not used in single pair cable?

2106


Why do we have earthing cable in branch cable and shield in the same cable?

2549


dear friends, i have seen flow as the selection critriea in presure guage (bourdon tube) and i would like to know what is the relation between flow and performance of pressure guage other parameters i found in the data sheet are pressure max. 1ksc temperature max. - 50 deg c line size - 80NB operating range - 1ksc pr. guage range - 0-2 ksc thank u,

2127


what is installation and commissioning of (fat & sat) of power plant dcs ? this question keeps in desirable conditions of one company .

4795