725KW Three DG set Synchronised but DG no-1 power showing
750KW DG n0-2 power showing 500KW DG no-03 showing 500KW.
DG is Shynchronised but why this different power showing?

Answer Posted / jince

Regarding paralleling DG sets we sticks only on the theoratical conditions of same voltage frequency phase angle and phase sequence. And now a days its easy to achieve using sync relays. Load sharing is the major thing in paralleling the DG sets. Many factors are depending on it
1. Droop of individual DG set must be same
Droop implies both voltage and frequency droop. it is the percentage of noload voltage or frequency. ex. 1% 2% 3% etc. Ex.1% voltage droop of 420V(noload)is 4.2V and it means on full load DG voltage comes down to 415.8V and not any more
Same is the case with frequency droop. All DG's droop must be same

2. On loadsharing we adjust voltage of DG's to met REACTIVE POWER AND SPEED(FREQUENCY) TO SHARE ACTIVE POWER

In order to share the load evenly we must control the voltage and frequency of individual DG's constantly

And it depends on load nature
In my personal experience for resistive loads (lamps)
loadsharing is not required as no variation occurs

For varying loads like lifts motors ac chillers compressssors etc constant loiadsharing is required


For clarification please reply

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is dc current source? Differentiate between ideal and non ideal current sources?

809


how to calculate voltage drop and followed by cable calculation?is there avail in formula?

1587


Difference between control junction box (cjb) and power junction box(pjb)?

2982


What is the universal motor?

644


why r we using shell transformer for low voltage

1541






What is NGR . What is the purpose of 10 sec ,60 sec rating of NGR.

1250


Dear All we are having a problem in G120 BOP showing alarm A0503, F0052, F0060 we can not remove fault alarm ,Please any body help us. kowsar

1254


number of I/O devices in siemense plc

1639


why power not passes in plastic and rubber material

1538


How to check 11000/1.732 to 110/1.732 Potentila transformer (PT)?

1754


Proviiding the Dedicated N earth and individual Body Earths ,Finally these all looped /Now my Question :- will it not harm in case of Transformer Fault current flows in Dediacted N Earthing to Looped Body Earthing.

1743


'documenˁ

1515


hi, could someone help me to find a control design for syncronising panel .

1268


how to test and calculat the head and discharge in borewell compressor

1698


Why it is possible to use PWM with a STATCOM and not with a conventional TCR based SVC

1575