Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

725KW Three DG set Synchronised but DG no-1 power showing
750KW DG n0-2 power showing 500KW DG no-03 showing 500KW.
DG is Shynchronised but why this different power showing?

Answer Posted / jince

Regarding paralleling DG sets we sticks only on the theoratical conditions of same voltage frequency phase angle and phase sequence. And now a days its easy to achieve using sync relays. Load sharing is the major thing in paralleling the DG sets. Many factors are depending on it
1. Droop of individual DG set must be same
Droop implies both voltage and frequency droop. it is the percentage of noload voltage or frequency. ex. 1% 2% 3% etc. Ex.1% voltage droop of 420V(noload)is 4.2V and it means on full load DG voltage comes down to 415.8V and not any more
Same is the case with frequency droop. All DG's droop must be same

2. On loadsharing we adjust voltage of DG's to met REACTIVE POWER AND SPEED(FREQUENCY) TO SHARE ACTIVE POWER

In order to share the load evenly we must control the voltage and frequency of individual DG's constantly

And it depends on load nature
In my personal experience for resistive loads (lamps)
loadsharing is not required as no variation occurs

For varying loads like lifts motors ac chillers compressssors etc constant loiadsharing is required


For clarification please reply

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How you calculating the 30 Hp 3 phase AC motor of power what size of cable is used for this motor?

1647


hi this is hema can anyone mail me previous years questions for the APPSC-A.E.E (in electrical stream.) ......thank u.

1899


1. Can a 12v DC choke operate a 60v/12w PL lamp ? 2. Can a 230v ballast fire / operate a 60v/12w PL lamps.

2174


how to measure the current by compact digital equipment with dislay which fit inside any equipment

1971


i installed 100kva ups. what KVA genset they should provid in input side? plz any update formula or ans with reason.

2323


In 90 kva alternator that produce the output voltage is 115(p-n),200(p-p) at 1500 rpms means what ampere it produced ?

2014


Is there possible to Test Transformer for Overfluxing Capability. Or is there any firm who does Overfluxing Test on Transformer?

3081


What is formula calculation size cable wire ?

1931


Pl. brief about break-down maintenance of machine tool.

1790


what is cathodic protaction?

1980


what is the transiant condition in alternator? and how it can be prevanted?

2074


why the protection turbo generators is most complex?

2025


if two transformers are placed parallel & both have fault impedance of 50KA will it increase or decrease show example?

1976


what are the breakdown voltage rating of mini- curcuit'transfarmer!

2154


How to do fabrication , busbar and wiring cost for : 1. LT Panels 2. C& R Panel

1903