how to calculate short circuit calculation of the transformer
by usuing the percentage impedence?
formula needed.
Answer Posted / elangovan kp
Isc (Shot circuit Current ) = Full load current of Tranformer / Impedance(%)
Ex: for 1000 KVA, 11/0.415 KV Transformer , Percentage Impedance - 6% :
Full load current of LV side of Transformer = 1000 * 1000 / ( 415 * 1.732)
= (1391 / 6) * 100
= 23187 Amps.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
Can we use 230VAC, 63A MCB for 120VAC, 63A supplied heaters load?
whatare the disadvantages occur,if the form factor of transmission will not be equal to 1.11
what is th basic difference between a d latch time line and a d flip flop time line???
What is meant by RVT and NDR ? expansion and details of it
how you taken aotitude test
what are the different kind of cables used for transmissions?
In synchronization circuit what is the function of Interposing voltage transformer(IVT)and Reverse voltage transformer(RVT)
it is in our knowledge tht right plug of supply of residential suppy system is phase n other is neutral...howevr the battery charger of mobile works in both ways...i mean it is not restricted in only one direction.ny of the holder of charger can hav phase .so y is it not lik tht phase of supply must b connected 2 phase of charger...?
A 7 storey building has a floor area of 35,000sq.ft on each storey. On the ground floor 11KV electrical sub-station is to be erected. A load of 3kw for every 400sq.ft (p.f is 0.8) is proposed for each floor. fire pump 7.5hp, water pump 5hp, lift 2 nos, each 10hp and 20shop load of each shop is 5kw. calculate a. load each floor b. total load of building c. L.T feeders for aech floor and from transformer to main. d. distribution diagram e. capacity of sub-station/capacitor bank f. line diagram
Why does the radius of armature is less than the radius of pole shoe?
what is DRP panels?
should %impedance be high or low in a power transformer? if so why?
How to work definite,over pluxing,revers power,OSR relay
which types of relay used in acb and vcb?
What is the disadventage of gland earthing(power cable) if any. ?