Can 2 nos. of 1 ton split ac be used through a 20 am supply
meter?
Answer Posted / s.ghosh
The answer is "Yes" for steady state current, but "No" for
starting current. You can use the 20A capacity line for 2
nos. 1T AC, but you have to ensure that at no instance, both
the ACs are switched on simultaneously.