How to check vortex flow meter is in good condition while
we do not having calibration setup?
Answer Posted / krishna reddy
Let me know first which make you have.
Instrument have min and max ranges on its name plate.
So wiht multimeter you can check 4-20ma of flow meter.It
must be 4 ma if flow is zero and 20ma if flow is max range.
supose your flow mete got 100L/hr.
for 4ma flow should be 0 L/hr
8ma - 25L/hr
12ma - 50L/hr
16ma - 75L/hr
20ma - 100L/hr
Like this you can check.
| Is This Answer Correct ? | 10 Yes | 3 No |
Post New Answer View All Answers
what is the difference between attemperator and desuperheater ?
Calibration procedure for Electro magnetic Flow meter
Make a ladder diagram on LSL valve will close, on PSL valve will open and start the motor
What are the charcterstics of a P&ID controller block for Governor speed raise or lower for a load sharing functionality between 4 Gas turbines in droop mode.
how to calibrate 0- 150 psi presure gauge by dead weght tester
model question paper of instrumentation for Jindal GET 2010.plz reply sudhanshukumar08@yahoo.com
Hi Friends i need Electronics&Instrumentation Engg question papers for BARC written test by coming 20th May 2008 pls post ur use full info to kkumarei@gmail.com. Or for suggestions pls give one missed call to 9962122264
Explain how thw analog to digital converter works with the circuit diagram
where uses EXe /EXd/Exo/Exn/Exp/Exq/EXia
what deference between panel earth and systemearth
TECHNICAL/ARTITUDE
what diffrence b/w plc s7200,300,400
How is PH sensor works ?
What is the right procedure for adjusting the gap voltage of bently nevada vibration sensor?
Can anyone convert a 5/2 way or 3/2 way valve into an ISO valve?