Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How to calculate cable sizes in sq.mm. with using motor KW?
Any formula there?

Answer Posted / sagir siddiqui

First of all you need to verified full load current of motor,
How can you calculate:
Ex: 1 Motor - 20HP 3ph. 415V 50Hz, 80% efficiency

Cal: A= HPx746/(sqrt3xVoltxPFxefficiency)

=20x746/1.732x415x0.8x0.8

=32.43Amp.

We all know that a motor has 1.5 times starting current,

Then 32.43x1.5 = 48.65Amp

Now you can see in the current currying capacity of cable from manufacturer cable's list.

3.5 x 35 sqmm xlpe cable is sufficient for full load.

Is This Answer Correct ?    347 Yes 171 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to confirm its base capacity?

1930


What are the advantages of speed control using thyristor?

1064


In india, according to trade theory above 5 HP motor reqired star delta starter. But we R connect 11 KV motor with 14MW in Direct to line ( With VCB starter combination) Can U Guess, How it is possible ?????

2075


what happen if the parallel generator phase angle shift by 1 degree in manual mode

1984


The ripple frequency in output of fullwave bridge rectifier is a. Half the input b. Twice the input c. Same as input

2214


we have 3.5MVA-11/6KV transformer. how can we calculate earth fault current and NGR calculation?

1478


what is package substation.how many types they have

2055


Please help me regarding my one concern. - During earth pit testing we noticed that the Clean earth pit and dirty earth pit showing continuity (Resistance value - 5ohm) . I want to know that if both earth pit have separate location and there is not internal looping between PIT then why such continuity is showing on it . Because of this issue the field side all earthing point showing short. In PLC panel we are providing two types of earthing cable which is coming from separate earth pit (Clean and Dirty earth pit) because of earth PIT showing short our PLC is not complying spec . please help regarding this issues.

1538


What is the difference between vector surge relay (78) and Pole slip relay (98G)

1148


can i use 2000/5A Clamp meter to measure HT cable

1971


we are small scale industry in production of rice & rice bran. Pls let me know how to take contract demand for our industry.. (for information we have total 600.hp)

4267


What type of DC motor would you see for a lift?

1047


What is Load sharing of Transformer ?

1980


working principle of oil startar

1836


What is the general system requirement of alternator?

1799