What is maximum permissible length of cable from transformer
(33kV/0.433kV) HT side to HT panel which contain VCB? In
which standard i shall get this information.
Answer Posted / a.p.nanjappa
this is a practical problem.
Generally , Station auxiliary or Unit auxiliary
transformers are located very near to load consummer PCC/mcc
building.
High voltage current is less and Low voltage current is
very high,say 1250kva-33/0.42kv,21/1800A,
5MVA,33/0.42KV,87A/7210A. therefore, the distance between
33kv MV SW.GR FEEDER to your transformer location could be
500-1000m as per voltage drop calculation.we have the
system around this distance.
the advatage is LOw voltage from power transformer to PCC
SW.GR IS BUS DUCT. Huge low voltage power cable are totally
eliminated. Maintenanve free. electrical engineering hand
book.siemens ,abb
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
There is any especial requirement for motor to drive through with VFD?
what are problems caused by the pdu in rack server
How to calculate the size of earth cable to earth the neutral of UPS ?
how to calculate single phase motor efficiency ?
What is shunt voltage and u v voltage witch one best
How to work definite,over pluxing,revers power,OSR relay
Pls tell me whether we can use EN3A material for shafts of Permanent magnet alternator.What will be the effect of magnetic and nonmagnetic material for shafts on magnetic properties of PM rotor .
What is earth?
Make a list observation on Transformer?
I use 20 nos led tube 4feet, in pathway 100mtr approximate, so what size cable i use for lighting
What are the advantages of instrument transformer?
What is the two pole structure?
slipring induction motor starting time Lrs operating why lrs starting time lrs outer body didn't get shock
I HAVE BEEN SELECTED FOR APGENCO A.E(ELECTRICAL) 2008.HOW MUCH WEIGHTAGE FOR INTERVIEW AND WRITTEN TEST.HOW I HAVE TO PREPARE. PLEASE GIVE INFORMATION IF U KNOW.WHAT ABT G.D THIS TIME.CALL RATIO 1:2
state working of halogen lamp?