in 132 kv substation ligtning arrestor(120 kv) connected to
line. but line voltage comes to 132 kv, it operate or
not???
Answer Posted / avradeep das
In any conductor of 132 KV transmission line rated voltage
with respect to ground(remember LA is connected between one
conductor/phase and earth)is 76(approx) KV so 120 KV is
adequate
| Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
How to calculate VCB rating for 33KV ,25 MW Power line?
If we have use two power cable for incomer, that time how many use cbct for earth leakage protection? 1 or 2 if 1 way? If 2 way?
i want wipro vlsi placement pattern please send me
700KW 6.6KV slip ring induction motor to use VFD to control the speed
why do you add the load short circuit impedance when considering short circuit amperage. It seems that you should only consider supply. If you need to consider loads and you don't know what loads are to be added , what would be a good sub-transient reactance rating for the loads?
whate is the meaning of balance/unbalance,in stabilizers type
what is the path of thunderlightening? once both a buffalo and a person were standing 5m apart but lightening hit and killed buffalo not person?
What is the significance of integral controller and derivative controller in a pid controller?
what is effect of length of air gap on performance of dc motor and generator?
define hysteresis loss, eddy current loss and windage loss
Can double compression glands be used with regular cables?
In HVDC LINE RECTIFIER CONTROL ON CONSTANT CURRENT AND INVERTER CONTROL CONSTANT EXITATION ANGLE CONTROL BUT HOW INVERTER CONTROL CONSTANT CURRENT?
at what base you will tell the direction of rotation of dc motors and generators?
What kinds of decision are made about CT from it's Knee point(voltage & current)?
How can we calculate ac current from the given DC current when AC voltage is given?