how to calculate busbar capacity for 1000Kva transformer having22/.433V
Answer Posted / shaik
First of all the voltage ratings given in the question might
be wrong. But the basic rule for calc. the ampacity is to
first find out the current..
Power/ Volts = Amp.
Then the ampacity of the conductor is choosen by taking 125%
of the current.
Here if i consider voltage of this tranformer to be 22/.433
kv. then on primary side the busbar capacity has to be,
1000x1000/22x1000 =45.45 A
45.45x 1.25=56.81 Amps.
Therefore the busbar capacity on primary side should not be
less than 60 Amps.
Similarly, secondary side is calc.
Is This Answer Correct ? | 5 Yes | 4 No |
Post New Answer View All Answers
Explain about Dubai electrical sysaem? Explain about Dubai drinking water system? Explain about Dubai Burj tallest building Electrical,Water.etc.. maintenance system?
why do we measure VIBRATION in -24vdc and why we adjust gap voltage -9vdc to 10-vdc? i am trying to get this information since 5 years, yet i haven't get reliable answer, i hope i can get from you.
can the measured percentage error during calibration of single phase energy meter be negative?
1) What are your personal strength? 2) What are your personal areas of improvement? 3) What are your expectations from from a particular job? 4) what are your carrier objectives?
im working in one private compeny in gujarat. i was complet diploma electric in 2010 from gujarat technical board. now i want electric supervisor licence in gujarat but i dont't know when i apply? plz give me address of the licence dippartment office in gujarat. gandhinagar
What is difference between YNyn0 and YNyn ??
In a tap changing transformer where is the tap connected, is it connected in the primary side or secondary side?
How do I calculate/select Droop CT ratio for various capacity of generators?
In our factory so many iron pillors are exists for supporting the shed/Hangar. If do more no of earthings at one piller instead of doing more earth pits in many locations and running earth strip around the hanger, I can save the money. Please suggest this method is acceptable as per Is specifications though the Earth resitance of the farthest piller is with in the limits as per IS specifications.
what is differnce btwen lll and lllg faults
what is the maximim current drawn by 1 phase and three phase welding machine
Why IR value of the (HT cable Plus synchronous motor) is less while individually having IR values in GΩ?
What are the raitings of Mcb,mccb and Acb in detail ??
why transformer ratings in kva? & DG ratings in kva? & Motor ratings in kw/HP?
Why neutral point is consider as zero potential?