Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calculate busbar capacity for 1000Kva transformer having22/.433V

Answer Posted / shaik

First of all the voltage ratings given in the question might
be wrong. But the basic rule for calc. the ampacity is to
first find out the current..

Power/ Volts = Amp.

Then the ampacity of the conductor is choosen by taking 125%
of the current.

Here if i consider voltage of this tranformer to be 22/.433
kv. then on primary side the busbar capacity has to be,

1000x1000/22x1000 =45.45 A

45.45x 1.25=56.81 Amps.

Therefore the busbar capacity on primary side should not be
less than 60 Amps.

Similarly, secondary side is calc.

Is This Answer Correct ?    5 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what are the usual topology of transformers at different substations in the power system and why that particular topology is choosen. what are the limitaions of that topology?

2094


I am having a 1500 KVA transformer whose secondary current is 2086A and my connected load is 1000 KVA, I am having 400 KVAR APFCR for PF improvement what ratio of CT should i install in LT EB Bus to get optimum PF improvement?

1732


According to underground cables a) stress b/w sheath & conductor is high b) inrush of core & conductor

1945


primery try cell?

2174


What is superposition theorem?

1171


Mention the disadvantages of low power factor?

1105


can indirect loading be called as phantom loading?

2170


how power is generated,and transmitted to our home..pls explain briefly in simple words.

2240


circuit diagram of trip circuit supervision relay

2031


Explain the fundamental difference between emf (electro motive force) and pd (potential difference) ?

1120


WILL SCHNEIDER MAKE ACB(MASTERPACT)TRIP ON REVERSE POWER?

2209


how we can calcultae the short circuit level for bus bar

2220


why should the lowest unit of a testing transformer ( cascaded transformer ) have higher power rating??

2277


sir, I am from EEE branch.On feb 17 iam going to write an Exam for hindustan petrolium corporation Ltd.So plz send me the written exam pattern/Q's/interview questions.please mail to eee_dharmendra@yahoo.com

1822


(In MEP services) HVAC in AC Plant room what else can we provide if the chiller is not considered?

2030