Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how can we can take BDV test in transformer?

Answer Posted / ramachandra reddy

On TRANSFORMER OIL BREAK DOWN VOLTAGE test is carried out which is done on field while filling the oil in transformer. This process is also called oil filtration.
1.Take sample from top of Transformer before filtration.
2.The BDV of oil should withstood min 50 KV
3.The gap between the test electrodes sample to be 2.5mm maintained
4.At least 5 sample(top/bottom) should be checked separately while filtration.
5. The samples should withstand 50 kv for 1 min.
5. Take the average of all the samples timings.You will get value.
7.Procedure
a.Voltage should be gradually increased from 0.
b. At one point Flash will take place and that point is
termed as Bread down Voltage

Is This Answer Correct ?    26 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the maximum breakdown voltage of 11KVA and 66 KVA power line and how it is calculated?

2271


in conventional fan regulators how the current varies with speed?

1977


we specify current in case of feeder but in case of distributor voltage, why?

1797


Why do we perform an open-circuit test and short-circuit test on the transformer?

1098


WHY TERTIARY OF POWER TRANSFORMERS IS LOADED WITH EQUIPMENTS LIKE CT,PT,ISOLATOR AND CB

1884


how to differentiate a mpcb,mcb with a contactor? Explain their working operation

2184


If 22 KV HT line, Current transformer is 25/5 then how to calculate multiplying factor.

1078


what is the terminal voltage of dc series generator running at rated speed at no load?

7587


How to calculate the current of Highpressure Mercury Vapour Lamp?what is the basis?whether we have to consider power factor or not?

2134


surge tank, hrc fuse, earthing transformer, firm power objective type

1613


in electrical control panel. how can i choose the cable rating. (example - 11kw motor, 18-25A mpcb}

2836


how to check three phase motor torque value?

2350


What will happen if the d.c. Shunt motor opened accidentally running on no-load has its shunt field winding?

1451


What is notching in dc machine?

1979


what is arc flash and what are the hazards involved

2140